verified connector library

Crowcon Vortex gas controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
system_status11U161
power_status12U161
detector_1_level2999I160.1
detector_1_status3000U161
detector_1_inhibit3003U161
detector_2_level3009I160.1
detector_2_status3010U161
detector_2_inhibit3013U161
detector_3_level3019I160.1
detector_3_status3020U161
detector_3_inhibit3023U161
detector_4_level3029I160.1
detector_4_status3030U161
detector_4_inhibit3033U161
detector_5_level3039I160.1
detector_5_status3040U161
detector_5_inhibit3043U161
detector_6_level3049I160.1
detector_6_status3050U161
detector_6_inhibit3053U161
detector_7_level3059I160.1
detector_7_status3060U161
detector_7_inhibit3063U161
detector_8_level3069I160.1
detector_8_status3070U161
detector_8_inhibit3073U161
detector_9_level3079I160.1
detector_9_status3080U161
detector_9_inhibit3083U161
detector_10_level3089I160.1
detector_10_status3090U161
detector_10_inhibit3093U161
detector_11_level3099I160.1
detector_11_status3100U161
detector_11_inhibit3103U161
detector_12_level3109I160.1
detector_12_status3110U161
detector_12_inhibit3113U161

link settings as documented (unverified): RTU; default 9600 8N2; FC 03,16; Binary RTU format. 1 start bit, 8 data bits, 2 stop bits, no parity.

bench facts as documented (unverified)
terminals2 wire
wiring noteshalf duplex RS485 link or RS232 hardware interfaces
max registers/read100
response timeout400 ms
protocol notesTurnaround time is 50 to 400 mS.
model register0
serial register32
identification notesUnit Type at register 1 (address 0), Serial Number at register 33 (address 32)
doc revision2
firmware applicabilityGCNCT1_1i1

generated by gemini:gemini-3.5-flash · harvested from https://www.crowcon.com/wp-content/uploads/2024/08/Vortex-Modbus-Map.pdf (Crowcon); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.