Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| flow_m3_h | 1100 | F32BE | 1 | m³/h |
| flow_nm3_h | 1108 | F32BE | 1 | Nm³/h |
| flow_m3_min | 1116 | F32BE | 1 | m³/min |
| flow_nm3_min | 1124 | F32BE | 1 | Nm³/min |
| flow_ltr_h | 1132 | F32BE | 1 | ltr/h |
| flow_nltr_h | 1140 | F32BE | 1 | Nltr/h |
| flow_ltr_min | 1148 | F32BE | 1 | ltr/min |
| flow_nltr_min | 1156 | F32BE | 1 | Nltr/min |
| flow_ltr_s | 1164 | F32BE | 1 | ltr/s |
| flow_nltr_s | 1172 | F32BE | 1 | Nltr/s |
| flow_cfm | 1180 | F32BE | 1 | cfm |
| flow_ncfm | 1188 | F32BE | 1 | Ncfm |
| flow_kg_h | 1196 | F32BE | 1 | kg/h |
| flow_kg_min | 1204 | F32BE | 1 | kg/min |
| flow_kg_s | 1212 | F32BE | 1 | kg/s |
| flow_kw | 1220 | F32BE | 1 | kW |
| consumption_m3 | 1268 | U32BE | 1 | m³ |
| consumption_nm3 | 1274 | U32BE | 1 | Nm³ |
| consumption_ltr | 1280 | U32BE | 1 | ltr |
| consumption_nltr | 1286 | U32BE | 1 | Nltr |
| consumption_cf | 1292 | U32BE | 1 | cf |
| consumption_ncf | 1298 | U32BE | 1 | Ncf |
| consumption_kg | 1304 | U32BE | 1 | kg |
| consumption_kwh | 1310 | U32BE | 1 | kWh |
| velocity_m_s | 1346 | F32BE | 1 | m/s |
| velocity_nm_s | 1354 | F32BE | 1 | Nm/s |
| velocity_ft_min | 1362 | F32BE | 1 | Ft/min |
| velocity_nft_min | 1370 | F32BE | 1 | NFt/min |
| gas_temp_c | 1418 | F32BE | 1 | °C |
| gas_temp_f | 1426 | F32BE | 1 | °F |
| system_pressure_mbar | 1474 | F32BE | 1 | mbar |
| system_pressure_bar | 1480 | F32BE | 1 | bar |
| system_pressure_psi | 1486 | F32BE | 1 | psi |
| delta_p | 1056 | F32BE | 1 |
| terminals | Via connection plug (M12 connector plug A and B) |
| A/B polarity | Pin 2 (Modbus A), Pin 4 (Modbus B) |
| termination | 120-Ω resistor for bus termination, M12 connector for electrical termination, or internal DIP switch |
| connector | M12 |
| shield/ground | Use shielded connection cables. |
| response timeout | 10000 ms |
| FC 43 device ID | not supported |
| power | 18... 36 V DC via SELV, 5 W. Optional PoE according to IEEE 802.3af, Class 2 (3.84...6.49 W) |
| environment | Ambient temperature: -20...+70 °C, Storage temperature: -40...+80 °C, Humidity: Max. 90% relative humidity, non-condensing, Altitude: Up to 4000 m above sea level, Protection class: IP65 |
| accuracy | ±1.5% of measured value, ±0.3% of final value |
| certifications | CE, UKCA |
| doc revision | 04/2026 | V2.02 | 020001046 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.