Daikin Applied MicroTech II chiller controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
active_setpoint2I160.1°F
actual_capacity10U160.1%
actual_rpm_comp_1246U161RPM
actual_rpm_comp_2250U161RPM
capacity_limit_output42U160.1%
capacity_limit_setpoint3U160.1%
chiller_mode_output147U161
chiller_mode_setpoint145U161
chiller_power244U161kW
chiller_status146U161
compressor_2_active_capacity_limit107U161%
compressor_2_vfd_speed99U161%
compressor_select_current26U161A
compressor_2_current95U161A
compressor_select_discharge_temp19I160.1°F
compressor_2_discharge_temp91I160.1°F
compressor_select_percent_rla25U160.1%
compressor_2_percent_rla94U160.1%
compressor_select_power27U161kW
compressor_2_power96U161kW
compressor_select_run_hours174U1610hours
compressor_2_run_hours235U1610hours
compressor_select160U161
compressor_select_starts173U161starts
compressor_2_starts234U161starts
compressor_select_status172U161
compressor_2_status233U161
compressor_select_suction_temp15I160.1°F
compressor_2_suction_temp88I160.1°F
compressor_select_voltage29U161VAC
compressor_2_voltage98U161VAC
condenser_entering_water_temp7I160.1
condenser_leaving_water_temp8I160.1°F
condenser_select_pump_run_hours176U1610hours
condenser_pump_2_run_hours232U1610hours
condenser_select_refrigerant_pressure21I160.1psi
condenser_2_refrigerant_pressure93I160.1psi
condenser_select_saturated_refrigerant_temp20I160.1°F
condenser_2_saturated_refrigerant_temp92I160.1°F
condenser_water_flow_rate24U161GPM
cool_setpoint1I160.1°F
evaporator_entering_water_temp4I160.1°F
evaporator_leaving_water_temp_unit6I160.1
evaporator_select_refrigerant_pressure17I160.1psi
evaporator_2_refrigerant_pressure90I160.1psi
evaporator_select_saturated_refrigerant_temp16I160.1°F
evaporator_2_saturated_refrigerant_temp89I160.1°F
evaporator_water_flow_rate18U161GPM
heat_recovery_entering_water_temp22I160.1°F
heat_recovery_leaving_water_temp23I160.1°F
heat_setpoint5I160.1°F
ice_setpoint50I160.1°F
outdoor_air_temperature39I160.1°F

link settings as documented (unverified): RTU; FC 01,02,03,04,05,06,15,16; Supports RTU mode only. Uses 8 data bits, 1 or 2 stop bits, and no parity. Baud rates from 1200 to 19200 bps.

bench facts as documented (unverified)
wiring notesRequires Modbus Communication Module (IM 743) installed.
identification notesSoftware part number is available via the Modbus integration tools.
certificationsProducts manufactured in an ISO Certified Facility.
doc revisionED 15063-7
firmware applicabilityMicroTech II Chiller Unit Controller

generated by gemini:gemini-3.5-flash · harvested from https://tahoeweb.daikinapplied.com/api/general/DownloadDocumentByName/media/Daikin_ED_15063-7_MTII_Chiller_Unit_Controller_Modbus_Tech_Sheet.pdf/ (Daikin Applied); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.