verified connector library

Daikin DCOM-LT/MB Modbus interface (split/Sky Air/Altherma)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
leaving_water_main_heating_setpoint1I161°C
leaving_water_main_cooling_setpoint2I161°C
operation_mode_holding3I161
space_heating_cooling_on_off4I161
room_thermostat_control_heating_setpoint6I161°C
room_thermostat_control_cooling_setpoint7I161°C
quiet_mode_operation9I161
dhw_reheat_setpoint10I161°C
dhw_reheat_on_off12I161
dhw_booster_mode_on_off13I161
weather_dependent_mode53I161
weather_dependent_mode_lwt_heating_setpoint_offset54I161°C
weather_dependent_mode_lwt_cooling_setpoint_offset55I161°C
unit_error21I161
unit_error_code22U161
unit_error_sub_code23I161
circulation_pump_running30I161
compressor_run31I161
booster_heater_run32I161
disinfection_operation33I161
defrost_startup35I161
hot_start36I161
three_way_valve37I161
operation_mode_input38I161
leaving_water_temperature_pre_phe40I160.01°C
leaving_water_temperature_pre_buh41I160.01°C
return_water_temperature42I160.01°C
domestic_hot_water_temperature43I160.01°C
outside_air_temperature44I160.01°C
liquid_refrigerant_temperature45I160.01°C
flow_rate49I160.01l/min
remocon_room_temperature50I160.01°C

link settings as documented (unverified): RTU; default 9600 8N1; FC 03,04,06,16; Modbus RTU over RS485 2-wire

⚠ The operation of the product in smart-grid applications must be according to EN60730-1:2011 and must not override the operation of any type 2 action controls nor interfere with any protective function of the control — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsCSA 0.5 to 2.5mm2, Torque 0.5Nm
A/B polarityPower terminals are polarity independent. 0V and +V can be wired to either terminal.
terminationRS485 termination is not required for normal operation. The DCOM RS485 transceiver has internal failsafe biasing.
connectorPA 6.6 UL94-V0
shield/groundTerminal 'C' must be connected to all other RS485 Common terminals using the drain wire. The shield should only be earthed at one location.
wiring notesDimensions 110 x 88 x 32 mm, Weight 80g, Enclosure PC ABS UL94-V0
max registers/read64
sentinel values32767: Register Unsupported, 32766: Register Unavailable, 32765: Wait for value
protocol notesIf the DCOM is timed out or synchronising with the Altherma master, values will return Wait for value until the value is loaded.
powerRegulated 15-24VDC, 80mA
environmentStorage: -10..60ºC, Operating: 0..55ºC, Humidity: 0-90% Non-condensing
certificationsEMC EN60730-1:2011, Safety EN60730-1:2011
doc revision534-252-A3
field reports — community-sourced, unverified (checked 2026-06-11)
  • After initial power-up or restart, the DCOM-LT/MB can take up to 8 minutes to fully synchronize with the Altherma Master unit. During this synchronization period, register reads will return the special sentinel value 32765 ('Wait for value'). [source]
  • confirmed: comms defaults (9600 baud, 8-N-1, Modbus RTU over RS485 2-wire) — confirmed by Daikin DCOM-LT/MB Reference Manual
  • confirmed: physical dimensions (110 x 88 x 32 mm, weight 80g, PC ABS UL94-V0 enclosure) — confirmed by Daikin DCOM-LT/MB Reference Manual
  • confirmed: power requirements (Regulated 15-24VDC, 80mA) — confirmed by Daikin DCOM-LT/MB Reference Manual
  • confirmed: polarity independence of power terminals — confirmed by Daikin DCOM-LT/MB Reference Manual
  • confirmed: sentinel values (32767: Register Unsupported, 32766: Register Unavailable, 32765: Wait for value) — confirmed by Daikin DCOM-LT/MB Reference Manual
  • confirmed: register map offsets (e.g., room_thermostat_control_heating_setpoint @ 6, room_thermostat_control_cooling_setpoint @ 7, quiet_mode_operation @ 9) — confirmed by Daikin DCOM-LT/MB Reference Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.