Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| unit_1_00_on_off_status | 2000 | U16 | 1 | |
| unit_1_00_operation_status | 2001 | U16 | 1 | |
| unit_1_00_room_temperature_set_point_read | 2002 | I16 | 0.1 | °C |
| unit_1_00_room_temperature | 2004 | I16 | 0.1 | °C |
| unit_1_00_leaving_water_set_point_heating_read | 2800 | I16 | 0.1 | °C |
| unit_1_00_leaving_water_set_point_cooling_read | 2801 | I16 | 0.1 | °C |
| unit_1_00_error_code | 3600 | U16 | 1 | |
| central_forced_off | 1000 | U16 | 1 | |
| unit_1_00_on_off_command | 2000 | U16 | 1 | |
| unit_1_00_operation_mode_setting | 2001 | U16 | 1 | |
| unit_1_00_room_temperature_set_point_write | 2002 | I16 | 0.1 | °C |
| unit_1_00_leaving_water_set_point_heating_write | 2400 | I16 | 0.1 | °C |
| unit_1_00_leaving_water_set_point_cooling_write | 2401 | I16 | 0.1 | °C |
| unit_1_00_domestic_hot_water_storage_set_point_write | 2402 | I16 | 0.1 | °C |
| unit_1_00_user_interface_lock | 2800 | U16 | 1 | °C |
⚠ The number of control commands per indoor unit is limited to 7000 per year. — Starkest reads only; we never write a control register.
| terminals | X3M (RS-485), F1/F2 (DIII-net), X1M (Power supply) |
| A/B polarity | A+, B- |
| termination | SS2 On = 120 Ohm, SS3 On = 100 Ohm, SS1 not used. Factory default is 0 Ohm (SS2=Off & SS3=Off) |
| connector | Terminal strips |
| shield/ground | Protective earth |
| wiring notes | BMS RS485 (2 wire, max 500m), DIII net (F1F2) maximum 64 indoor units and maximum 10 outdoors |
| max registers/read | 32 |
| response timeout | 25 ms |
| inter-frame delay | 5 ms |
| broadcast | supported |
| protocol notes | The number of control commands per indoor unit is limited to 7000 per year. |
| power | 220 – 240 VAC 50/60 Hz |
| environment | Temp range 0 till 60°C, Indoor installation, IP X0 |
| doc revision | 4P642495-1A– 2022.02 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.