Daikin VRV Modbus interface EKMBDXB

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
unit_1_00_on_off_status2000U161
unit_1_00_operation_status2001U161
unit_1_00_room_temperature_set_point_read2002I160.1°C
unit_1_00_room_temperature2004I160.1°C
unit_1_00_leaving_water_set_point_heating_read2800I160.1°C
unit_1_00_leaving_water_set_point_cooling_read2801I160.1°C
unit_1_00_error_code3600U161
central_forced_off1000U161
unit_1_00_on_off_command2000U161
unit_1_00_operation_mode_setting2001U161
unit_1_00_room_temperature_set_point_write2002I160.1°C
unit_1_00_leaving_water_set_point_heating_write2400I160.1°C
unit_1_00_leaving_water_set_point_cooling_write2401I160.1°C
unit_1_00_domestic_hot_water_storage_set_point_write2402I160.1°C
unit_1_00_user_interface_lock2800U161°C

link settings as documented (unverified): RTU; default 9600 8E1; FC 03,04,06,16; Silent internal time: 5ms at 9600bps, 2.5ms at 19200bps. Response time is Silent Interval Time + 20ms.

⚠ The number of control commands per indoor unit is limited to 7000 per year. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsX3M (RS-485), F1/F2 (DIII-net), X1M (Power supply)
A/B polarityA+, B-
terminationSS2 On = 120 Ohm, SS3 On = 100 Ohm, SS1 not used. Factory default is 0 Ohm (SS2=Off & SS3=Off)
connectorTerminal strips
shield/groundProtective earth
wiring notesBMS RS485 (2 wire, max 500m), DIII net (F1F2) maximum 64 indoor units and maximum 10 outdoors
max registers/read32
response timeout25 ms
inter-frame delay5 ms
broadcastsupported
protocol notesThe number of control commands per indoor unit is limited to 7000 per year.
power220 – 240 VAC 50/60 Hz
environmentTemp range 0 till 60°C, Indoor installation, IP X0
doc revision4P642495-1A– 2022.02

generated by gemini:gemini-3.5-flash · harvested from https://www.daikin-ce.com/content/dam/document-library/Installer-reference-guide/ac/vrv/ekmbdxb/EKMBDXB_Design%20guide_4PEN642495-1A_English.pdf (Daikin); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.