Delta DTM temperature controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
ch1_pv616I160.1°C
ch2_pv617I160.1°C
ch3_pv618I160.1°C
ch4_pv619I160.1°C
ch5_pv620I160.1°C
ch6_pv621I160.1°C
ch7_pv622I160.1°C
ch8_pv623I160.1°C
ch1_sv624I160.1
ch2_sv625I160.1
ch3_sv626I160.1
ch4_sv627I160.1
ch5_sv628I160.1
ch6_sv629I160.1
ch7_sv630I160.1
ch8_sv631I160.1
ch1_out1_power632U160.1
ch2_out1_power633U160.1
ch3_out1_power634U160.1
ch4_out1_power635U160.1
ch5_out1_power636U160.1
ch6_out1_power637U160.1
ch7_out1_power638U160.1
ch8_out1_power639U160.1
ch1_out2_power640U160.1
ch2_out2_power641U160.1
ch3_out2_power642U160.1
ch4_out2_power643U160.1
ch5_out2_power644U160.1
ch6_out2_power645U160.1
ch7_out2_power646U160.1
ch8_out2_power647U160.1
ch1_status648U161
ch2_status649U161
ch3_status650U161
ch4_status651U161
ch5_status652U161
ch6_status653U161
ch7_status654U161
ch8_status655U161
ch1_ct1_value712U160.1
ch2_ct1_value713U160.1
ch3_ct1_value714U160.1
ch4_ct1_value715U160.1
ch5_ct1_value716U160.1
ch6_ct1_value717U160.1
ch7_ct1_value718U160.1
ch8_ct1_value719U160.1
ch1_ct2_value720U160.1
ch2_ct2_value721U160.1
ch3_ct2_value722U160.1
ch4_ct2_value723U160.1
ch5_ct2_value724U160.1
ch6_ct2_value725U160.1
ch7_ct2_value726U160.1
ch8_ct2_value727U160.1

link settings as documented (unverified): RTU/ASCII/TCP; default 38400 8E1; unit ID 1; FC 03,06,16; Supports RS485, Ethernet (Modbus TCP), and USB (for configuration only, no signal isolation).

⚠ USB connection has no signal isolation and cannot be used for long-term monitoring. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRS485 communications terminal, Power input terminal, Sensor input terminal
connectorRJ-45, Mini USB, RS485 terminal
isolationChannels are completely isolated from each other. USB has no signal isolation.
wiring notesRequires needle-type terminals with diameter < 2.35mm.
max registers/read64
protocol notesInitialization takes approximately 30 seconds after power on, during which external communications are unavailable.
identification notesModel and serial registers not explicitly defined in the provided pages.
power24V DC (90% ~ 110% of rated voltage). Host Max 6W + 5W * measurement modules + 3W * I/O modules.
environmentOperating temperature: 0°C to +50°C. Storage temperature: -20°C to +65°C. Operating humidity: 35% to 85% RH (no dew). Operating altitude: Below 2,000 meters. Pollution level: 2.
accuracySampling frequency: 0.1 sec./all 8 inputs.
doc revisionV1.0 (2020/02/22)

⚠ disputed: default_unit_id: 1 — disputed by DTM Software Operating Manual v1.3, which states that when the host station number dial switch is set to 0 (the default 'All OFF' setting), the RS-485 station number address is 16 (DEC) / 10 (HEX).

field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [4800, 9600, 19200, 38400, 57600, 115200] and default baud rate of 38400 — confirmed by DTM Temperature Controller Operating Manual V1.0
  • confirmed: Sampling frequency: 0.1 sec./all 8 inputs — confirmed by DTM Temperature Controller Operating Manual V1.0
  • confirmed: USB connection has no signal isolation and cannot be used for long-term monitoring — confirmed by DTM Temperature Controller Operating Manual V1.0
  • confirmed: Initialization takes approximately 30 seconds after power on, during which external communications are unavailable — confirmed by DTM Temperature Controller Operating Manual V1.0
  • confirmed: Requires needle-type terminals with diameter < 2.35mm — confirmed by DTM Temperature Controller Operating Manual V1.0
  • confirmed: Operating temperature: 0°C to +50°C, Storage temperature: -20°C to +65°C, Operating humidity: 35% to 85% RH, Operating altitude: < 2,000 m, Pollution level: 2 — confirmed by DTM Temperature Controller Operating Manual V1.0
  • confirmed: Register map addresses (PV starting at 616, SV starting at 624, OUT1 power starting at 632, OUT2 power starting at 640, Channel status starting at 648) — confirmed by DTM Software Operating Manual v1.3

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.