Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| air_pressure | 5000 | F32LE | 1 | mbar |
| relative_humidity | 1020 | F32LE | 1 | % |
| temperature_c | 1002 | F32LE | 1 | °C |
| temperature_f | 1004 | F32LE | 1 | °F |
| dew_point_temperature_c | 1104 | F32LE | 1 | °C |
| dew_point_temperature_f | 1106 | F32LE | 1 | °F |
| frost_point_dew_point_temperature_c | 1130 | F32LE | 1 | °C |
| frost_point_dew_point_temperature_f | 1132 | F32LE | 1 | °F |
| absolute_humidity_g_m3 | 1112 | F32LE | 1 | g/m³ |
| absolute_humidity_gr_ft3 | 1114 | F32LE | 1 | gr/ft³ |
| mixing_ratio_g_kg | 1120 | F32LE | 1 | g/kg |
| mixing_ratio_gr_lb | 1122 | F32LE | 1 | gr/lb |
| wet_bulb_temperature_c | 1108 | F32LE | 1 | °C |
| wet_bulb_temperature_f | 1110 | F32LE | 1 | °F |
| ice_bulb_temperature_c | 1682 | F32LE | 1 | °C |
| ice_bulb_temperature_f | 1684 | F32LE | 1 | °F |
| specific_enthalpy_kj_kg | 1124 | F32LE | 1 | kJ/kg |
| specific_enthalpy_btu_lb | 1128 | F32LE | 1 | BTU/lb |
| specific_enthalpy_ft_lbf_lb | 1126 | F32LE | 1 | ft lbf/lb |
| water_vapour_partial_pressure_mbar | 1100 | F32LE | 1 | mbar |
| water_vapour_partial_pressure_psi | 1102 | F32LE | 1 | psi |
| volume_concentration_ppm | 1150 | F32LE | 1 | ppm |
| terminals | Screw terminals max. 1.5 mm² (AWG 16) |
| termination | Both ends of the bus shall be terminated with a resistor Ra=120 Ω. |
| connector | M12 socket, M12 plug, RJ45 |
| isolation | galvanically isolated |
| shield/ground | GND RS485 (shielded) |
| model register | 9 |
| serial register | 0 |
| firmware register | 8 |
| power | 8 - 35 V DC / 12 - 30 V AC, or 100 - 240 V AC (Option AM3) |
| environment | Operation: -40...+60 °C (-40...+140 °F) without display, -20...+50 °C (-4...+122 °F) with display |
| accuracy | RH: ±(0.95 + 0.0013 * mv) %RH, T: ±0.1 °C |
| certifications | CE, UKCA, FCC Part15 ClassA, ICES-003 ClassA |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.