E-Mon PowerSmart+ power meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
v1_voltage13952F32LE1
v2_voltage13954F32LE1
v3_voltage13956F32LE1
i1_current13958F32LE1
i2_current13960F32LE1
i3_current13962F32LE1
kw_l113964F32LE1
kw_l213966F32LE1
kw_l313968F32LE1
kvar_l113970F32LE1
kvar_l213972F32LE1
kvar_l313974F32LE1
kva_l113976F32LE1
kva_l213978F32LE1
kva_l313980F32LE1
pf_l113982F32LE1
pf_l213984F32LE1
pf_l313986F32LE1
total_kw14336F32LE1
total_kvar14338F32LE1
total_kva14340F32LE1
total_pf14342F32LE1
average_voltage_ln14356F32LE1
average_voltage_ll14358F32LE1
average_current14360F32LE1
neutral_current14466F32LE1
frequency14468F32LE1
voltage_unbalance14470F32LE1
current_unbalance14472F32LE1
kwh_import14720F32LE1
kwh_export14722F32LE1
kvarh_import14728F32LE1
kvarh_export14730F32LE1
kvah_total14736F32LE1

link settings as documented (unverified): RTU; baud 300/600/1200/2400/4800/9600/19200/38400/57600/115200; FC 03,04,06,16,08

bench facts as documented (unverified)
wiring notesCOM1 supports RS-485. COM2 supports RS-232, RS-422, RS-485, RF, Ethernet, and Profibus.
broadcastnot supported
model register46082
serial register46080
firmware register46100
doc revisionBG0542 Rev. A1

generated by gemini:gemini-3.5-flash · harvested from https://prod-edam.honeywell.com/content/dam/honeywell-edam/hbt/en-us/documents/manuals-and-guides/reference-guides/hbt-bms-E-Mon-PowerSmart-Essential-MODBUS-Reference-Guide-BG0542-REV-A1.pdf (Honeywell/E-Mon); manual-faithful — the document's claims, panel risk: HIGH — independent re-derivation disagrees on specific fields; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.