Eliwell EW 4800 series controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
analogue_input_control298I160.1°C/°F
analogue_output1486U161num
contatore_autorepeat408U161num
regulation_set_point_116392I160.1°C/°F
offset_on_set_point_116394I160.1°C/°F
tripping_band_above_set_point_116396U160.1°C/°F
differential_of_set_point_116398I160.1°C/°F
maximum_value_settable_for_set_point_116400I160.1°C/°F
minimum_value_settable_for_set_point_116402I160.1°C/°F
max_alarm_regulator_116404I160.1°C/°F
min_alarm_regulator_116406I160.1°C/°F
regulation_set_point_216408I160.1°C/°F
offset_on_set_point_216410I160.1°C/°F
tripping_band_above_set_point_216412U160.1°C/°F
differential_of_set_point_216414I160.1°C/°F
maximum_value_settable_for_set_point_216416I160.1°C/°F
minimum_value_settable_for_set_point_216418I160.1°C/°F
max_alarm_regulator_216420I160.1°C/°F
min_alarm_regulator_216422I160.1°C/°F

link settings as documented (unverified): RTU; default 9600 8E1; unit ID 1; FC 03,16,43; If parameters PtS, PtY and Stp are changed, the controller must be turned off and then on again after they are changed to operate correctly.

bench facts as documented (unverified)
terminalsRS485 cable shielded and twisted (e.g.: Belden cable model 8762)
connector5-path connector TTL cable (30cm)
wiring notesBus Adapter BA150
max registers/read60
broadcastsupported
protocol notesParameters belonging to two different non-consecutive blocks cannot be read using a single command.
identification notesField code 0: Manufacturer ID ('Invensys'), Field code 1: Instrument model ID ('003E_000A'), Field code 2: Instrument version ID ('00F8_0011')
FC 43 device IDsupported
doc revision2010/04/0

generated by gemini:gemini-3.5-flash · harvested from https://mosinv.ru/Documentation/EW48/8MA10081_EW48_Modbus_EN_0410.pdf (Eliwell); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.