Eliwell EW 4800 series controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
analogue_input_control298I160.1°C/°F
analogue_output1486U161num
contatore_autorepeat408U161num
regulation_set_point_116392I160.1°C/°F
offset_on_set_point_116394I160.1°C/°F
tripping_band_above_set_point_116396U160.1°C/°F
differential_of_set_point_116398I160.1°C/°F
maximum_value_settable_for_set_point_116400I160.1°C/°F
minimum_value_settable_for_set_point_116402I160.1°C/°F
max_alarm_regulator_116404I160.1°C/°F
min_alarm_regulator_116406I160.1°C/°F
regulation_set_point_216408I160.1°C/°F
offset_on_set_point_216410I160.1°C/°F
tripping_band_above_set_point_216412U160.1°C/°F
differential_of_set_point_216414I160.1°C/°F
maximum_value_settable_for_set_point_216416I160.1°C/°F
minimum_value_settable_for_set_point_216418I160.1°C/°F
max_alarm_regulator_216420I160.1°C/°F
min_alarm_regulator_216422I160.1°C/°F

link settings as documented (unverified): RTU; default 9600 8E1; unit ID 1; FC 03,16,43; If parameters PtS, PtY and Stp are changed, the controller must be turned off and then on again after they are changed to operate correctly.

bench facts as documented (unverified)
terminalsRS485 cable shielded and twisted (e.g.: Belden cable model 8762)
connector5-path connector TTL cable (30cm)
wiring notesBus Adapter BA150
max registers/read60
broadcastsupported
protocol notesParameters belonging to two different non-consecutive blocks cannot be read using a single command.
identification notesField code 0: Manufacturer ID ('Invensys'), Field code 1: Instrument model ID ('003E_000A'), Field code 2: Instrument version ID ('00F8_0011')
FC 43 device IDsupported
doc revision2010/04/0
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rate of 9600 and default baud of 9600 — confirmed by Eliwell EW 4800 Modbus Manual [1.1.1]
  • confirmed: Default unit ID of 1 — confirmed by default parameters FAA=0 and dEA=1 (FAA * 16 + dEA = 1) in Eliwell EW 4800 Modbus Manual
  • confirmed: Modbus RTU framing and function codes 3, 16, 43 — confirmed by Eliwell EW 4800 Modbus Manual
  • confirmed: Power cycle requirement after changing PtS, PtY, and Stp — confirmed by Eliwell EW 4800 Modbus Manual
  • confirmed: Default parity 'E' and stop bits 1 — confirmed by Eliwell EW 4800 Modbus Manual
  • confirmed: Document revision '2010/04/0' — confirmed by Eliwell EW 4800 Modbus Manual footer
  • confirmed: Device identification fields (Manufacturer ID 'Invensys', Model ID '003E_000A', Version ID '00F8_0011') — confirmed by Eliwell EW 4800 Modbus Manual
  • confirmed: Physical connection via 5-path connector TTL cable (30cm), Bus Adapter BA150, and Belden 8762 RS485 cable — confirmed by Eliwell EW 4800 Modbus Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.