Eliwell ID 985 refrigeration controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
set_point6178I160.1
operating_differential6146U160.1
max_set_point6180I160.1
min_set_point6182I160.1
end_of_defrost_temperature6150I160.1
end_of_defrost_temperature_2nd_evap6366I160.1
evaporator_fan_shutdown_temperature6154I160.1
evaporator_fan_startup_temperature6156I160.1
analogue_input_18504I160.1
analogue_input_28506I160.1
analogue_input_38508I160.1
analogue_input_1_control8510I160.1
analogue_input_2_control8512I160.1
analogue_input_3_control8514I160.1
status_digital_inputs9009U161
alarms_18814U161
alarms_28815U161
controller_status8818U161
relay_status8763U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,16,43; The baud rate must be set to 9600 bauds. Parity is configurable via parameter PtY (default none), and stop bits via parameter StP (default 1b).

bench facts as documented (unverified)
terminals5-path connector TTL cable (30cm)
connector5-path connector TTL cable
shield/groundshielded and twisted (e.g.: Belden cable model 8762)
wiring notesBus Adapter BA150 used for RS485 connection.
max registers/read60
broadcastsupported
protocol notesA maximum of 60 consecutive registers can be read or written. Parameters belonging to two different non-consecutive blocks cannot be read using a single command.
identification notesDevice ID fields can be read using Modbus command 43: Field 0 (Manufacturer ID = 'Invensys'), Field 1 (Instrument model ID = '0028_0402'), Field 2 (Instrument version ID = '00E2_0001').
FC 43 device IDsupported
doc revision2005/03/0
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: The baud rate must be set to 9600 bauds. Parity is configurable via parameter PtY (default none), and stop bits via parameter StP (default 1b). — confirmed by Eliwell ID 985/E LX Modbus Serial Communication Protocol manual
  • confirmed: Device ID fields can be read using Modbus command 43: Field 0 (Manufacturer ID = 'Invensys'), Field 1 (Instrument model ID = '0028_0402'), Field 2 (Instrument version ID = '00E2_0001'). — confirmed by Eliwell ID 985/E LX Modbus Serial Communication Protocol manual
  • confirmed: set_point @ 6178, operating_differential @ 6146, max_set_point @ 6180, min_set_point @ 6182, end_of_defrost_temperature @ 6150, end_of_defrost_temperature_2nd_evap @ 6366, evaporator_fan_shutdown_temperature @ 6154, evaporator_fan_startup_temperature @ 6156, analogue_input_1 @ 8504, analogue_input_2 @ 8506, analogue_input_3 @ 8508, analogue_input_1_control @ 8510, analogue_input_2_control @ 8512, analogue_input_3_control @ 8514, status_digital_inputs @ 9009, alarms_1 @ 8814, alarms_2 @ 8815, controller_status @ 8818, relay_status @ 8763 — confirmed by Eliwell ID 985/E LX Modbus Serial Communication Protocol manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.