Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| modb_pv_value | 5000 | F32BE | 1 | |
| modb_sv_value | 5002 | F32BE | 1 | m |
| modb_tv_value | 5004 | F32BE | 1 | dB |
| modb_qv_value | 5006 | F32BE | 1 | °C |
| modb_signalquality | 5008 | F32BE | 1 | |
| modb_actualdiagnostics | 5010 | F32BE | 1 | |
| modb_location_longitude | 5012 | F32BE | 1 | ° |
| modb_location_latitude | 5014 | F32BE | 1 | ° |
| lcrs_distance_value | 5105 | F32BE | 1 | m |
| ho_qvvalue | 5117 | F32BE | 1 | °C |
| lcrs_signalquality | 5104 | U16 | 1 | |
| lcrs_primlevout_value | 5102 | F32BE | 1 | |
| lcrs_absechoamplitude | 5109 | F32BE | 1 | dB |
| lcrs_snappedlevel | 5111 | F32BE | 1 | m |
| lcrs_snappedabsoluteechoamplitude | 5115 | F32BE | 1 | dB |
| lcrs_snappeddistance | 5113 | F32BE | 1 | m |
| ho_pvvalue | 5100 | F32BE | 1 | |
| ho_tvvalue | 5107 | F32BE | 1 | dB |
| lcrs_currenteventcategory | 5124 | U16 | 1 | |
| lcrs_actualdiagnostics | 5119 | U32BE | 1 | |
| lcrs_previousdiagnostics | 5121 | U32BE | 1 | |
| le_full | 5264 | F32BE | 1 | m |
| le_empty | 5262 | F32BE | 1 | m |
| lcrs_mapping_endpointctrl | 5267 | F32BE | 1 | m |
| terminals | Plus (brown), Minus (blue), Modbus D0/A (+) (white), Modbus D1/B (-) (black) |
| A/B polarity | D0/A (+), D1/B (-) |
| termination | Bus terminating resistor as per RS485-IS specification (510 Ohm / 200 Ohm / 510 Ohm) |
| connector | Cable gland or Conduit adapter |
| isolation | RS485-IS specification for use in hazardous environments |
| wiring notes | Up to 32 users can be connected on the RS485 bus. Type-A fieldbus cable max length 1200 m (3937 ft) or 1000 m (3281 ft) in hazardous environment. |
| protocol notes | Minimum polling interval 500 ms |
| serial register | 5126 |
| firmware register | 5142 |
| identification notes | Order code at 5132, Device name at 5146, ENP version at 5154 |
| power | 5 to 30 VDC |
| environment | Permitted ambient temperature (Ta) and max process temperature on nameplate. Sensor can reach close to medium temperature up to 80 °C (176 °F) during operation. |
| certifications | CE mark, EAC conformity, RCM |
| doc revision | BA02115F/00/EN/02.21, 71535780, 2021-08-30 |
| firmware applicability | 01.00.zz |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.