Endress+Hauser Micropilot FMR20 radar

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
modb_pv_value5000F32BE1
modb_sv_value5002F32BE1m
modb_tv_value5004F32BE1dB
modb_qv_value5006F32BE1°C
modb_signalquality5008F32BE1
modb_actualdiagnostics5010F32BE1
modb_location_longitude5012F32BE1°
modb_location_latitude5014F32BE1°
lcrs_distance_value5105F32BE1m
ho_qvvalue5117F32BE1°C
lcrs_signalquality5104U161
lcrs_primlevout_value5102F32BE1
lcrs_absechoamplitude5109F32BE1dB
lcrs_snappedlevel5111F32BE1m
lcrs_snappedabsoluteechoamplitude5115F32BE1dB
lcrs_snappeddistance5113F32BE1m
ho_pvvalue5100F32BE1
ho_tvvalue5107F32BE1dB
lcrs_currenteventcategory5124U161
lcrs_actualdiagnostics5119U32BE1
lcrs_previousdiagnostics5121U32BE1
le_full5264F32BE1m
le_empty5262F32BE1m
lcrs_mapping_endpointctrl5267F32BE1m

link settings as documented (unverified): RTU/ASCII; default 9600 8E1; unit ID 200; FC 03,06,16; Minimum polling interval 500 ms

bench facts as documented (unverified)
terminalsPlus (brown), Minus (blue), Modbus D0/A (+) (white), Modbus D1/B (-) (black)
A/B polarityD0/A (+), D1/B (-)
terminationBus terminating resistor as per RS485-IS specification (510 Ohm / 200 Ohm / 510 Ohm)
connectorCable gland or Conduit adapter
isolationRS485-IS specification for use in hazardous environments
wiring notesUp to 32 users can be connected on the RS485 bus. Type-A fieldbus cable max length 1200 m (3937 ft) or 1000 m (3281 ft) in hazardous environment.
protocol notesMinimum polling interval 500 ms
serial register5126
firmware register5142
identification notesOrder code at 5132, Device name at 5146, ENP version at 5154
power5 to 30 VDC
environmentPermitted ambient temperature (Ta) and max process temperature on nameplate. Sensor can reach close to medium temperature up to 80 °C (176 °F) during operation.
certificationsCE mark, EAC conformity, RCM
doc revisionBA02115F/00/EN/02.21, 71535780, 2021-08-30
firmware applicability01.00.zz

generated by gemini:gemini-3.5-flash · harvested from https://bdih-download.endress.com/files/DLA/005056A500261EEC819361BAC907DDAD/BA02115FEN_0221.pdf (Endress+Hauser); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.