Estun ProNet AC servo drive

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
speed_feedback2054I161
input_speed_reference_value2055I161
input_torque_reference_percentage2056I161
internal_torque_reference_percentage2057I161
number_of_encoder_rotation_pulses2058U161
input_signal_state2059U161
encoder_signal_state2060U161
output_signal_state2061U161
pulse_setting2062U161
low_bits_of_present_location2063U161
high_bits_of_present_location2064I161
error_pulse_counter_low_16_bits2065U161
error_pulse_counter_high_16_bits2066I161
setting_pulse_counter_low_bits2067U161
setting_pulse_counter_high_bits2068I161
load_inertia_percentage2069U161
servomotor_overloading_proportion2070U161
current_alarm2071U161
servomotor_winding_temperature2072I161

link settings as documented (unverified): RTU/ASCII; default 9600 8O1; unit ID 1; Maximum of 31 servo drives can be connected. Terminating resistance of 120 ohms is used at both ends of the 485 network. If transmission speed is above 9600bps, please use the communication cable within 15 meters.

bench facts as documented (unverified)
terminalsCN3, CN4
termination120 ohm terminating resistance
isolationIsolated ground (ISO_GND)
shield/groundConnect shield to connector shell
wiring notesCN3 is used as communication cable input terminal and CN4 is used as communication cable output terminal.
max registers/read12
protocol notesData content n-word=2n-byte, n <= 12
powerSingle-phase 200~230VAC, Three-phase 200~230VAC, Three-phase 380~480VAC, Three-phase 380~440VAC (+10% -15%, 50/60Hz)
environmentTemperature: -20~55°C, Humidity: 5%~95%RH, Vibration: 4.9m/s^2 or less, Condensation and Freezing: None
certificationsCE
doc revisionV2.02
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms.baud_rates [4800, 9600, 19200] and default_baud 9600 — confirmed by Estun ProNet Series User Manual parameter Pn700.0
  • confirmed: comms.parity 'O' (Odd) and stop_bits 1 — confirmed by Estun ProNet Series User Manual parameter Pn700.1 default setting 5 (8, O, 1)
  • confirmed: comms.default_unit_id 1 — confirmed by Estun ProNet Series User Manual parameter Pn701 default setting
  • confirmed: quirks.max_read_registers 12 — confirmed by Estun ProNet Series User Manual stating 'n-word=2n-byte, n <= 12'
  • confirmed: physical.terminals CN3, CN4 and isolation ISO_GND — confirmed by Estun ProNet Series User Manual CN3/CN4 pinout definitions
  • confirmed: power specifications — confirmed by Estun ProNet Series User Manual voltage ranges for 200V and 400V drive units
  • confirmed: register map addresses (0806h-0818h / 2054-2072) — confirmed by Estun ProNet Series User Manual Servo state data communication address table

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.