Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| frequency_command_pu | 1793 | I16 | 1 | |
| frequency_command_hz | 1797 | U16 | 0.01 | |
| operation_command | 1798 | U16 | 1 | |
| frequency_reference_pu | 2049 | I16 | 1 | |
| frequency_reference_hz | 2053 | U16 | 0.01 | Hz |
| output_frequency_pu | 2054 | I16 | 1 | |
| torque_real_value | 2055 | I16 | 0.01 | % |
| torque_current | 2056 | I16 | 0.01 | % |
| output_frequency_hz | 2057 | U16 | 0.01 | Hz |
| input_power | 2058 | U16 | 0.01 | % |
| output_current_effective_value | 2059 | U16 | 0.01 | % |
| output_voltage_effective_value | 2060 | U16 | 1 | V |
| operation_command_m | 2061 | U16 | 1 | |
| operation_status | 2062 | U16 | 1 | |
| cumulative_operation_time | 2068 | U16 | 1 | h |
| dc_link_circuit_voltage | 2069 | U16 | 1 | V |
| motor_temperature | 2070 | I16 | 1 | °C |
| heat_sink_temperature | 2110 | U16 | 1 | °C |
| load_factor | 2111 | I16 | 0.01 | % |
| motor_output | 2112 | I16 | 0.01 | % |
| operation_status_w | 3841 | U16 | 1 | |
| frequency_reference_w | 3842 | U16 | 0.01 | Hz |
| output_frequency_before_slip_compensation | 3843 | U16 | 0.01 | Hz |
| output_frequency_after_slip_compensation | 3844 | U16 | 0.01 | Hz |
| output_voltage_w | 3846 | U16 | 0.1 | V |
| torque_w | 3847 | I16 | 1 | % |
| dc_link_circuit_voltage_w | 3911 | U16 | 1 | |
| heat_sink_maximum_temperature | 3913 | U16 | 1 |
⚠ If alarm resetting is performed with the operation command (S06) uncleared, the inverter will start to operate just upon alarm resetting. Before alarm resetting, confirm that the operation command is cleared. Otherwise, an accident may result. — Starkest reads only; we never write a control register.
| terminals | RJ-45 connector or terminal block |
| A/B polarity | DX+ is positive, DX- is negative |
| termination | A terminating resistor of 112 ohms is incorporated. Connection/release is switched by switch. |
| connector | 8-wire RJ-45 connector or terminal block |
| isolation | The RS-232C side of the converter must be isolated from the RS-485 side. |
| shield/ground | SD terminal for relaying the shield of the shielded cable, insulated from other circuits. |
| max registers/read | 50 |
| broadcast | supported |
| model register | M23 |
| firmware register | M25 |
| power | Vcc 5V power source for the keypad is connected to the RJ-45 connector (via pins 1, 2, 7, and 8). |
| certifications | Compliant with EMC Directives (when using KB-STP-01K) |
| doc revision | 24A7-E-0082 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.