Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| process_value | 1000 | I16 | 1 | °C/°F |
| current_set_value | 1001 | I16 | 1 | °C/°F |
| current_deviation | 1002 | I16 | 1 | °C/°F |
| manipulated_value_1 | 1003 | I16 | 0.01 | % |
| manipulated_value_2 | 1004 | I16 | 0.01 | % |
| heater_current | 1009 | I16 | 0.1 | A |
| sv_controlled_on_face_panel | 1002 | I16 | 1 | °C/°F |
| proportional_band | 1005 | U16 | 0.1 | % |
| integral_time | 1006 | U16 | 0.1 | s |
| derivative_time | 1007 | U16 | 0.1 | s |
| cooling_proportional_band_coefficient | 1009 | U16 | 0.1 | A |
| dead_band | 1010 | I16 | 0.01 | s |
| heater_burnout_alarm_set_value | 1038 | U16 | 0.1 | A |
⚠ For avoiding electric shock and malfunctions, do not turn on the power supply until all wiring have been completed. — Starkest reads only; we never write a control register.
| terminals | 7 (+), 8 (-) |
| A/B polarity | 7 is +, 8 is - |
| termination | Both ends of the cable should be terminated with terminating resistors 100 ohm 1/2W |
| connector | Terminal block |
| isolation | Functional isolation between transmission circuit and others (withstand voltage: 500V AC) |
| shield/ground | The shield wire of the cable should be grounded at one place on the master station unit side. |
| wiring notes | Recommended cable: UL2464, UL2448, etc. Recommended noise filter: ZRAC2203-11/TDK |
| max registers/read | 60 |
| broadcast | not supported |
| protocol notes | While the data is being written in non-volatile memory after write via communication, the next write is attempted and will result in no response. |
| FC 43 device ID | not supported |
| doc revision | INP-TN512642a-E |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.