Fuji PXR temperature controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
process_value1000I161°C/°F
current_set_value1001I161°C/°F
current_deviation1002I161°C/°F
manipulated_value_11003I160.01%
manipulated_value_21004I160.01%
heater_current1009I160.1A
sv_controlled_on_face_panel1002I161°C/°F
proportional_band1005U160.1%
integral_time1006U160.1s
derivative_time1007U160.1s
cooling_proportional_band_coefficient1009U160.1A
dead_band1010I160.01s
heater_burnout_alarm_set_value1038U160.1A

link settings as documented (unverified): RTU; default 9600 8O1; unit ID 1; FC 01,02,03,04,05,06,16; Transmission speed, data length, and stop bit are fixed.

⚠ For avoiding electric shock and malfunctions, do not turn on the power supply until all wiring have been completed. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminals7 (+), 8 (-)
A/B polarity7 is +, 8 is -
terminationBoth ends of the cable should be terminated with terminating resistors 100 ohm 1/2W
connectorTerminal block
isolationFunctional isolation between transmission circuit and others (withstand voltage: 500V AC)
shield/groundThe shield wire of the cable should be grounded at one place on the master station unit side.
wiring notesRecommended cable: UL2464, UL2448, etc. Recommended noise filter: ZRAC2203-11/TDK
max registers/read60
broadcastnot supported
protocol notesWhile the data is being written in non-volatile memory after write via communication, the next write is attempted and will result in no response.
FC 43 device IDnot supported
doc revisionINP-TN512642a-E

generated by gemini:gemini-3.5-flash · harvested from https://www.instrumart.com/assets/PXR%20MODBUS%20Protocol.pdf (Fuji Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.