GE Multilin 750/760 feeder management relay

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
general_status_alarm512U161
contact_1516U161
close_coil_monitor517U161
output_relay_status_1_trip518U161
neutral_voltage766U160.01
phase_a_rms_current768U161
phase_b_rms_current769U161
phase_c_rms_current770U161
ground_current772U161
a_n_rms_voltage773U160.01
b_n_rms_voltage774U160.01
c_n_rms_voltage775U160.01

link settings as documented (unverified): RTU/TCP; default 9600 8N1; unit ID 1; Supports Modbus RTU on serial ports (COM1, COM2, Front RS232) and Modbus TCP/IP over Ethernet (up to 4 sessions).

⚠ Relay contacts must be considered unsafe to touch when the 750/760 is energized! — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsScrew terminals on rear panel (slotted, pan head nickel plated #8-32x0.375")
A/B polarityCorrect polarity must be observed on RS485/RS422 (B1 for +, B2 for -) and logic inputs.
terminationTerminating impedance at each end typically 120 Ohms and 1 nF.
connectorRJ45 for Ethernet, 9-pin D-connector for front RS232, screw terminals for rear serial ports.
isolationAnalog outputs are fully isolated. Opto-coupled data interface for serial ports.
shield/groundShield (Ground) terminal B9 for serial, G12 for Safety Ground, G11 for Filter Ground. Shield should be grounded at one point only.
wiring notesFully drawout unit with automatic CT shorts.
protocol notesEEPROM DATA ERROR message may be displayed after upgrading/downgrading firmware due to Modbus address rearrangement.
identification notesThe label found on the left side of the relay specifies its order code or model number.
powerLO: 20 to 60 V DC or 20 to 48 V AC; HI: 88 to 300 V DC or 70 to 265 V AC
environmentOperating temperature: -40°C to +60°C. Storage/Shipping: -40°C to +80°C. Humidity: up to 90% non-condensing. Pollution degree: 2. IP Rating: 40-X.
accuracyAnalog outputs accuracy: ±1% of full scale.
certificationsMeets CE drawout specifications, UL registered (UL # A3775), ISO9001:2000 registered.
doc revisionManual P/N: 1601-0120-AE, Manual Order Code: GEK-106471N, September 2011
firmware applicabilitySoftware Revision: 7.4x

generated by gemini:gemini-3.5-flash · harvested from https://www.gegridsolutions.com/products/manuals/750/750man-ae.pdf (GE Grid Solutions); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.