Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| general_status_alarm | 512 | U16 | 1 | |
| contact_1 | 516 | U16 | 1 | |
| close_coil_monitor | 517 | U16 | 1 | |
| output_relay_status_1_trip | 518 | U16 | 1 | |
| neutral_voltage | 766 | U16 | 0.01 | |
| phase_a_rms_current | 768 | U16 | 1 | |
| phase_b_rms_current | 769 | U16 | 1 | |
| phase_c_rms_current | 770 | U16 | 1 | |
| ground_current | 772 | U16 | 1 | |
| a_n_rms_voltage | 773 | U16 | 0.01 | |
| b_n_rms_voltage | 774 | U16 | 0.01 | |
| c_n_rms_voltage | 775 | U16 | 0.01 |
⚠ Relay contacts must be considered unsafe to touch when the 750/760 is energized! — Starkest reads only; we never write a control register.
| terminals | Screw terminals on rear panel (slotted, pan head nickel plated #8-32x0.375") |
| A/B polarity | Correct polarity must be observed on RS485/RS422 (B1 for +, B2 for -) and logic inputs. |
| termination | Terminating impedance at each end typically 120 Ohms and 1 nF. |
| connector | RJ45 for Ethernet, 9-pin D-connector for front RS232, screw terminals for rear serial ports. |
| isolation | Analog outputs are fully isolated. Opto-coupled data interface for serial ports. |
| shield/ground | Shield (Ground) terminal B9 for serial, G12 for Safety Ground, G11 for Filter Ground. Shield should be grounded at one point only. |
| wiring notes | Fully drawout unit with automatic CT shorts. |
| protocol notes | EEPROM DATA ERROR message may be displayed after upgrading/downgrading firmware due to Modbus address rearrangement. |
| identification notes | The label found on the left side of the relay specifies its order code or model number. |
| power | LO: 20 to 60 V DC or 20 to 48 V AC; HI: 88 to 300 V DC or 70 to 265 V AC |
| environment | Operating temperature: -40°C to +60°C. Storage/Shipping: -40°C to +80°C. Humidity: up to 90% non-condensing. Pollution degree: 2. IP Rating: 40-X. |
| accuracy | Analog outputs accuracy: ±1% of full scale. |
| certifications | Meets CE drawout specifications, UL registered (UL # A3775), ISO9001:2000 registered. |
| doc revision | Manual P/N: 1601-0120-AE, Manual Order Code: GEK-106471N, September 2011 |
| firmware applicability | Software Revision: 7.4x |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.