verified connector library

Hitachi SJ100/L100/SJ200/L200 drive

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
output_frequency_monitor3000U32BE0.1
output_current_monitor3002U32BE0.1
rotation_direction_monitor3004U32BE1
pid_feedback_monitor3006U32BE0.01
intelligent_input_terminal_status3008U32BE1
intelligent_output_terminal_status3010U32BE1
scaled_output_frequency_monitor3012U32BE0.001
trip_counter3158U32BE1
error_code_of_trip_13160U32BE1
error_code_of_trip_23162U32BE1
error_code_of_trip_33164U32BE1
output_frequency_setting_from_volume3198U32BE0.01
output_frequency_monitor_l100_sj1003200U32BE0.01
frequency_setpoint_l100_sj1003202U32BE0.01
run_mode8000U32BE1
trip_history_1_time8004U32BE1
trip_history_1_cause8006U32BE1
trip_history_1_frequency8008U32BE1
trip_history_1_current8010U32BE1
trip_history_1_voltage8012U32BE1

link settings as documented (unverified): TCP; FC 03,04,06,16; Supports MODBUS/TCP communication protocol.

bench facts as documented (unverified)
terminalsPower Alm Rly +24V- GNDC CM NC NO
connectorRJ45 Jack (marked ETHERNET), RJ11 Jack (marked SERIAL)
wiring notesConnects to inverter via RJ11 to RJ45 cable.
max registers/read125
powerRequires 24 VDC via terminals marked '+ 24 V -'.
doc revisionHAL1052, December 2005
field reports — community-sourced, unverified (checked 2026-06-11)
  • Register address offset: Users must use 0-based addressing (subtracting 1 from the documentation's 1-based start addresses) to avoid reading/writing incorrect registers. [source]
  • Coil mapping / Alarm trip issue: Writing to the third coil (thinking it is a direction command) actually triggers an external trip command (alarm) on the VFD because of a mismatch/inconsistency in register/coil numbering. [source]
  • confirmed: Supports MODBUS/TCP communication protocol with function codes 3, 4, 6, 16 — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052) [1.2.9]
  • confirmed: Physical connectors include RJ45 (marked ETHERNET) and RJ11 (marked SERIAL) with RJ11-to-RJ45 connection to the inverter — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Requires 24 VDC via terminals marked '+ 24 V -' — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Terminals are marked 'Power Alm Rly +24V- GNDC CM NC NO' — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Max read registers is 125 — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)
  • confirmed: Register map matches 0-based start addresses of 32-bit parameters (e.g., output_frequency_monitor at 3000, run_mode at 8000) — confirmed by SJ/L-EN Ethernet Communications Module Instruction Manual (HAL1052)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.