Invertek Optidrive E3 drive

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
control_word0U161
frequency_setpoint1I160.1Hz
ramp_control_time3U160.01s
error_code5U161
output_frequency6I160.1Hz
motor_current7U160.1A
motor_torque8I160.0244140625%
motor_power9U160.01kW
digital_input_status10U161
analog_1_input_result19U160.1%
analog_2_input_result20U160.1%
pre_ramp_speed_reference21I160.1Hz
dc_bus_voltage22U161V
drive_power_stage_temperature23I161°C
relay_output_status28U161
kwh_meter31U160.1kWh
mwh_meter32U161MWh
running_time_hours33U161h
running_time_minutes_seconds34U161s
run_time_since_last_enable_hours35U161h
run_time_since_last_enable_minutes_seconds36U161s
internal_drive_temperature38I161°C
output_voltage42U161V

link settings as documented (unverified): RTU; default 115200 8??; unit ID 1; FC 03,06; Optidrive E3 supports Modbus RTU communication, using the 03 Read Holding Registers and 06 Write Single Holding Register commands.

⚠ Power down for 5 minutes before removing cover — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsOn-board RJ45
connectorRJ45
shield/groundInvertek recommend using Cat 6 shielded twisted pair cables with pin to pin construction.
response timeout300 ms
model register16
serial register24-27
firmware register14-15
power110 – 480 Volt 1 & 3 Phase
environmentAmbient Temperature Range: Operation IP20 Drives: -10 - +50°C, IP55 & IP66 Drives: -10 - +40°C. Relative Humidity Limit: 95% Maximum, non-condensing.
accuracybetter than 1% of full scale
certificationsEN 61800-5-1:2007, EN 60990:2000
doc revisionIssue 06
firmware applicabilityversion 3.08 Firmware

generated by gemini:gemini-3.5-flash · harvested from https://www.wolfautomation.com/content/invertek-optidrive-e3-advanced-userguide-21.pdf (Invertek); manual-faithful — the document's claims, panel risk: LOW — panel concurs, no field disagreements; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.