verified connector library

Janitza UMG605 meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

cross-referenced (XPF (Quantum Bit Solutions))

Imported from a third-party source and NOT verified by us — not even structure-checked. An unverified claim, shown so you can find the device; trust it no more than the source it came from.

pointaddress (0-based)typescaleunit
voltage_l1_n_v_g_uln_018999F32BE1V
apparent_current_l1_n_a_g_iln_019011F32BE1A
real_power_l1_n_w_g_pln_019019F32BE1kW
real_energy_l1_wh_g_wh_019053F32BE1kWh
measured_frequency_hz_g_freq19049F32BE1Hz
pfln_03892F32BE1
emax_d_status_07065I161
ext_temperatur4208F32BE1
harmonic_thd_u_l1_n_g_thd_uln_019109F32BE1
vector_sum_ini1i2i3_a_g_i_sum319017F32BE1
baud4856863I32BE1
voltage_l2_n_v_g_uln_119001F32BE1V

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.