Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| analog_input | 28672 | F32LE | 1 | |
| min_value | 28674 | F32LE | 1 | |
| max_value | 28676 | F32LE | 1 | |
| tara_value | 28678 | F32LE | 1 | |
| math_result_1 | 28680 | F32LE | 1 | |
| math_result_2 | 28682 | F32LE | 1 | |
| math_result_3 | 28684 | F32LE | 1 | |
| math_result_4 | 28686 | F32LE | 1 | |
| controller_setpoint_value | 28688 | F32LE | 1 | |
| controller_actual_value | 28690 | F32LE | 1 | |
| control_deviation | 28692 | F32LE | 1 | |
| output_level_display | 28694 | F32LE | 1 | |
| setpoint_value_1 | 28696 | F32LE | 1 | |
| setpoint_value_2 | 28698 | F32LE | 1 | |
| setpoint_value_3 | 28700 | F32LE | 1 | |
| setpoint_value_4 | 28702 | F32LE | 1 | |
| ramp_end_value | 28704 | F32LE | 1 | |
| current_ramp_setpoint_value | 28706 | F32LE | 1 | |
| ext_analog_input_1 | 28708 | F32LE | 1 | |
| ext_analog_input_2 | 28710 | F32LE | 1 | |
| timer_run_time | 28716 | F32LE | 1 | |
| timer_remaining_running_time | 28718 | F32LE | 1 | |
| timer_value | 28720 | F32LE | 1 | |
| operating_time | 28756 | F32LE | 1 | |
| limit_value_monitoring_functions | 27984 | U16 | 1 | |
| timer_status_word | 27985 | U16 | 1 | |
| digital_outputs | 27986 | U16 | 1 | |
| digital_control_signals | 27987 | U16 | 1 | |
| digital_inputs | 27988 | U16 | 1 | |
| external_digital_inputs | 27989 | U16 | 1 | |
| controller_outputs | 27990 | U16 | 1 |
| terminals | RxD/TxD+ (terminal 11), RxD/TxD- (terminal 12) |
| termination | terminating resistors are required at the beginning and end of an RS485 transmission path. |
| shield/ground | A twisted connecting cable with shielding must be used to connect the RS485 interface. To avoid transmission errors, only the signals listed above and, if necessary, GND may be routed in the connecting cable. |
| max registers/read | 127 |
| response timeout | 1000 ms |
| broadcast | supported |
| sentinel values | 1.0 x 10^37: Measuring range underflow, 2.0 x 10^37: Measuring range overflow, 3.0 x 10^37: Value invalid, 4.0 x 10^37: Division by zero, 5.0 x 10^37: Math error, 6.0 x 10^37: Error: terminal temperature/compensation signal, 7.0 x 10^37: Probe short circuit, 8.0 x 10^37: Probe break |
| doc revision | V5.00/EN/00688816/2024-04-10 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.
To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.
Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.