| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| analog_input | 28672 | F32LE | 1 | |
| min_value | 28674 | F32LE | 1 | |
| max_value | 28676 | F32LE | 1 | |
| tara_value | 28678 | F32LE | 1 | |
| math_result_1 | 28680 | F32LE | 1 | |
| math_result_2 | 28682 | F32LE | 1 | |
| math_result_3 | 28684 | F32LE | 1 | |
| math_result_4 | 28686 | F32LE | 1 | |
| controller_setpoint_value | 28688 | F32LE | 1 | |
| controller_actual_value | 28690 | F32LE | 1 | |
| control_deviation | 28692 | F32LE | 1 | |
| output_level_display | 28694 | F32LE | 1 | |
| setpoint_value_1 | 28696 | F32LE | 1 | |
| setpoint_value_2 | 28698 | F32LE | 1 | |
| setpoint_value_3 | 28700 | F32LE | 1 | |
| setpoint_value_4 | 28702 | F32LE | 1 | |
| ramp_end_value | 28704 | F32LE | 1 | |
| current_ramp_setpoint_value | 28706 | F32LE | 1 | |
| ext_analog_input_1 | 28708 | F32LE | 1 | |
| ext_analog_input_2 | 28710 | F32LE | 1 | |
| timer_run_time | 28716 | F32LE | 1 | |
| timer_remaining_running_time | 28718 | F32LE | 1 | |
| timer_value | 28720 | F32LE | 1 | |
| operating_time | 28756 | F32LE | 1 | |
| limit_value_monitoring_functions | 27984 | U16 | 1 | |
| timer_status_word | 27985 | U16 | 1 | |
| digital_outputs | 27986 | U16 | 1 | |
| digital_control_signals | 27987 | U16 | 1 | |
| digital_inputs | 27988 | U16 | 1 | |
| external_digital_inputs | 27989 | U16 | 1 | |
| controller_outputs | 27990 | U16 | 1 |
| terminals | RxD/TxD+ (terminal 11), RxD/TxD- (terminal 12) |
| termination | terminating resistors are required at the beginning and end of an RS485 transmission path. |
| shield/ground | A twisted connecting cable with shielding must be used to connect the RS485 interface. To avoid transmission errors, only the signals listed above and, if necessary, GND may be routed in the connecting cable. |
| max registers/read | 127 |
| response timeout | 1000 ms |
| broadcast | supported |
| sentinel values | 1.0 x 10^37: Measuring range underflow, 2.0 x 10^37: Measuring range overflow, 3.0 x 10^37: Value invalid, 4.0 x 10^37: Division by zero, 5.0 x 10^37: Math error, 6.0 x 10^37: Error: terminal temperature/compensation signal, 7.0 x 10^37: Probe short circuit, 8.0 x 10^37: Probe break |
| doc revision | V5.00/EN/00688816/2024-04-10 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.