Mitsubishi Electric A/C via Intesis ME-AC-MBS interface

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
ac_unit_on_off0U161
ac_unit_mode1U161
ac_unit_fan_speed2U161
ac_unit_vane_position3U161
ac_unit_temperature_setpoint4U161°C
ac_unit_ambient_temperature5U161°C
window_contact6U161
device_disablement7U161
ir_remote_command_disablement8U161
ac_unit_operation_time9U161h
ac_unit_alarm_status10U161
error_code11U161
ac_model12U161
open_window_switch_off_timeout13U161min
modbus_rtu_baud_rate14U161
device_modbus_slave_address15U161
software_version50U161

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 0; FC 03,04,06,16; Although function 16 is allowed, the interface does not allow write operations on more than 1 register with the same request, this means that length field should always be 1 when using this function for writes.

bench facts as documented (unverified)
terminalsplug-in terminal block of 2 poles
A/B polarityA B
terminationon-board terminator resistor of 120Ω selectable via DIP-switch P5
connectorplug-in terminal block
isolation1000 VDC isolation voltage, 1000 MΩ isolation resistance
wiring notesDirect connection to the AC indoor unit via CN92 (Mr.Slim) or CN105 (other models).
broadcastsupported
protocol notesWrite operations on more than 1 register with the same request are not allowed.
firmware register50
powerExternal power not required.
environmentOperating Temperature: -40 ... 85ºC, Operating Humidity: <95% RH, non-condensing
doc revisionrev.8
firmware applicabilityv.1.13
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [2400, 9600, 19200, 57600] with default 9600, 8N1 framing — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)
  • confirmed: Function codes 3, 4, 6, 16 supported, but writes with function 16 are restricted to a length of 1 register — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)
  • confirmed: Direct connection to the AC indoor unit via CN92 or CN105 — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)
  • confirmed: Register map addresses (ac_unit_on_off @ 0, ac_unit_alarm_status @ 10, error_code @ 11, software_version @ 50) — confirmed by IntesisBox ME-AC-MBS-1 v.1.13 User Manual (rev.8)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.