verified connector library

Northern Design Cube 400 meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
kwh514U32BE1kWh
kvah516U32BE1kVAh
kvarh_inductive518U32BE1kvarh
kvarh_capacitive520U32BE1kvarh
import_kvarh522U32BE1kvarh
export_kwh524U32BE1kWh
export_kvarh526U32BE1kvarh
hours_run528U32BE1h
system_kw2816I161kW
system_kva2817I161kVA
system_kvar2818I161kvar
system_pf2819I160.001
frequency2820I160.1Hz
phase_1_volts2821I161V
phase_1_amps2822I161A
phase_1_kw2823I161kW
phase_2_volts2824I161V
phase_2_amps2825I161A
phase_2_kw2826I161kW
phase_3_volts2827I161V
phase_3_amps2828I161A
phase_3_kw2829I161kW
phase_1_pf2830I160.001
phase_2_pf2831I160.001
phase_3_pf2832I160.001
ph1_ph2_volts2833I161V
ph2_ph3_volts2834I161V
ph3_ph1_volts2835I161V
neutral_current2836I161A
phase_1_kva3072I161kVA
phase_2_kva3073I161kVA
phase_3_kva3074I161kVA
phase_1_kvar3075I161kvar
phase_2_kvar3076I161kvar
phase_3_kvar3077I161kvar
v1_thd4352U160.1%
v2_thd4353U160.1%
v3_thd4354U160.1%
i1_thd4355U160.1%
i2_thd4356U160.1%
i3_thd4357U160.1%

link settings as documented (unverified): RTU; baud 4800/9600/19200; FC 03,04,06,08,16; Modbus RTU/JBUS, 16-Bit CRC

⚠ The Cube400 is intended for connection to dangerous voltages giving a risk of electric shock. Refer to the safety/installation instructions in the Cube400 Installation Guide before connecting the communications. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRising clamp, max wire 4mm2
terminationTwo 120 Ohm resistors recommended
isolation3.5kV (1 minute) RS485 Port from all other circuit
shield/groundShield should be connected to ground at the host (PC) only. The cable shield should not be used as the 0V connection.
wiring notes3-Pairs of terminals, internally shorted, are provided for convenience.
max registers/read20
response timeout250 ms
inter-frame delay5 ms
broadcastsupported
protocol notesException codes 1 and 2 are supported.
model register3590
firmware register3592
identification notesMeter Type is at register 3591.
powerInternally supplied from Cube400 Auxiliary. Requires additional 1W max
doc revisionRevision 5, July 2016
field reports — community-sourced, unverified (checked 2026-06-11)
  • When attempting to read a non-existent register (e.g., register 2815 / 0x0AFF) over Modbus TCP, the device echoes back the exact request bytes instead of returning a standard Modbus exception response, causing an 'Incorrect PDU length' error in the master. [source]
  • confirmed: Baud rates [4800, 9600, 19200], framing [RTU], function codes [3, 4, 6, 8, 16], Modbus RTU/JBUS, 16-Bit CRC — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Control warning regarding dangerous voltages and safety instructions — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Document revision 'Revision 5, July 2016' — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Identification registers (model at 3590, type at 3591, firmware at 3592) — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Physical specifications (3.5kV isolation, 3-pairs of internally shorted terminals, shield ground recommendations, rising clamp terminals up to 4mm2, and two 120 Ohm resistors recommended) — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Power requirements (internally supplied from auxiliary, additional 1W max) — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Quirks (broadcast supported, 5ms inter-frame delay, max 20 read registers, exception codes 1 and 2 supported, 250ms response timeout) — confirmed by Cube400 Modbus Comms Manual REV5
  • confirmed: Register map summary (energy registers starting at 514, instantaneous values starting at 2816, additional instantaneous values starting at 3072, and THD values starting at 4352) — confirmed by Cube400 Modbus Comms Manual REV5

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.