Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| pv | 8192 | I16 | 0.1 | °C |
| status | 8193 | U16 | 1 | |
| internal_set_point | 8194 | I16 | 0.1 | |
| heater_current_1_value_monitor | 8195 | U16 | 0.1 | |
| mv_monitor_heating | 8196 | I16 | 0.1 | |
| mv_monitor_cooling | 8197 | I16 | 0.1 | |
| set_point | 8451 | I16 | 0.1 | |
| alarm_value_1 | 8452 | I16 | 1 | |
| alarm_value_upper_limit_1 | 8453 | I16 | 1 | |
| alarm_value_lower_limit_1 | 8454 | I16 | 1 | |
| alarm_value_2 | 8455 | I16 | 1 | |
| alarm_value_upper_limit_2 | 8456 | I16 | 1 | |
| alarm_value_lower_limit_2 | 8457 | I16 | 1 | |
| decimal_point_monitor | 9232 | U16 | 1 | |
| leakage_current_1_monitor | 10012 | U16 | 0.1 | |
| heater_current_2_value_monitor | 10020 | U16 | 0.1 | |
| leakage_current_2_monitor | 10022 | U16 | 0.1 | |
| soak_time_remain | 10024 | U16 | 1 |
⚠ Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, unexpected operation may occasionally result in property damage or accidents. — Starkest reads only; we never write a control register.
| terminals | RS-485 (2-wire, half-duplex) |
| A/B polarity | A is (-), B is (+) |
| termination | 120 ohm (1/2 W) terminating resistance |
| connector | Screw terminal blocks, screwless clamp terminal blocks, push-in plus terminal blocks, or plug-in sockets depending on model |
| isolation | Non-isolated model (CJ1W-CIF11) |
| shield/ground | Shielded twisted-pair cable |
| max registers/read | 106 |
| response timeout | 20 ms |
| inter-frame delay | 2 ms |
| broadcast | supported |
| protocol notes | Allow a wait time of at least 2 ms before the next command is sent after the host receives a response from the E5@C. |
| identification notes | The unit number can be set between H'00 to H'63 hexadecimal (0 to 99 decimal). |
| environment | Indoor use only |
| certifications | UL listed, Lloyd's standards |
| doc revision | H175-E1-17 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.