Omron MX2 (Type V2) inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
output_frequency_setting0U32BE0.01
inverter_status_a2U161
inverter_status_b3U161
inverter_status_c4U161
pid_feedback5U160.01
output_frequency_monitor4096U32BE0.01Hz
output_current_monitor4098U160.01A
run_direction_monitor4099U161
pid_feedback_value_monitor4100U32BE0.1
multi_function_input_monitor4102U161
multi_function_output_monitor4103U161
output_frequency_monitor_after_conversion4104U32BE0.01
real_frequency_monitor4106U32BE0.01Hz
torque_reference_monitor4108U161%
torque_bias_monitor4109U161%
output_torque_monitor4111U161%
output_voltage_monitor4112U160.1V
input_power_monitor4113U160.1kW
integrated_power_monitor4114U32BE1
total_run_time_monitor4116U32BE1h
total_power_on_time_monitor4118U32BE1h
fin_temperature_monitor4120U160.1°C
life_assessment_monitor4124U161
dc_voltage_monitor4133U160.1V
regenerative_braking_load_rate_monitor4134U160.1%
electronic_thermal_load_rate_monitor4135U160.1%

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 01,03,05,06,08,15,16,23; Silent Interval 0 to 1,000 ms selectable via parameter C078.

bench facts as documented (unverified)
terminalsRS+/RS- on the control circuit terminal block
terminationBuilt-in terminating resistor: 120 Ω, enabled via slide switch
connectorControl circuit terminal block
shield/groundUse a shielded cable and connect it to the terminal SC.
max registers/read16
response timeout0 ms
inter-frame delay0 ms
broadcastsupported
protocol notesSimultaneous broadcast to up to five groups is supported by setting the slave address to 0.
FC 43 device IDnot supported
powerSingle-phase 200 to 240 VAC, 3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
environmentOperating ambient temperature: -10 to 50°C, Operating ambient humidity: 20% to 90% (with no condensation), Location: At a maximum altitude of 1,000 m, indoors (without corrosive gases or dust)
certificationsCE, UKCA, UL, CA, KC, RCM
doc revisionI666-E1-03

⚠ disputed: Built-in terminating resistor: 120 Ω, enabled via slide switch — disputed by Omron MX2 User's Manual which specifies the built-in terminating resistor is 200 Ω [10.2.6]

field reports — community-sourced, unverified (checked 2026-06-11)
  • When replacing an MX2 inverter, if Free V/F control is selected (A044 = 05 or 06), the inverter treats b112 (Free-setting V/F frequency 7) as the maximum frequency. If b112 is left at its default value of 0 Hz, the inverter will accept Modbus frequency writes but clamp the actual frequency reference to 0 Hz, resulting in a zero frequency output even when the Run command is active. [source]
  • The Omron MX2 uses overlapping Modbus addresses for coils and holding registers (e.g., Coil 0001h is the RUN command, while Holding Register 0001h is the Output Frequency Setting). This can cause confusion in PLC environments (like CoDeSys V2.3) that do not clearly separate coil and holding register spaces or lack native support for single-coil write function code 05h. [source]
  • confirmed: baud_rates [2400, 4800, 9600, 19200, 38400, 57600, 76800, 115200] and default_baud 9600 — confirmed by Omron MX2 User's Manual (Cat. No. I666-E1-03) parameter C071
  • confirmed: default_unit_id 1 — confirmed by Omron MX2 User's Manual parameter C072
  • confirmed: function_codes [1, 3, 5, 6, 8, 15, 16, 23] — confirmed by Omron MX2 User's Manual Section B-3-2
  • confirmed: Silent Interval 0 to 1,000 ms selectable via parameter C078 — confirmed by Omron MX2 User's Manual parameter C078
  • confirmed: certifications 'CE, UKCA, UL, CA, KC, RCM' — confirmed by Omron MX2 Type V2 official specifications
  • confirmed: Simultaneous broadcast to up to five groups is supported by setting the slave address to 0 — confirmed by Omron MX2 User's Manual Section B-3
  • confirmed: terminals 'RS+/RS- on the control circuit terminal block' — confirmed by Omron MX2 User's Manual control circuit terminal block diagram
  • confirmed: shield_ground 'Use a shielded cable and connect it to the terminal SC' — confirmed by Omron MX2 User's Manual wiring diagram

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.