Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| output_frequency_setting | 0 | U32BE | 0.01 | |
| inverter_status_a | 2 | U16 | 1 | |
| inverter_status_b | 3 | U16 | 1 | |
| inverter_status_c | 4 | U16 | 1 | |
| pid_feedback | 5 | U16 | 0.01 | |
| output_frequency_monitor | 4096 | U32BE | 0.01 | Hz |
| output_current_monitor | 4098 | U16 | 0.01 | A |
| run_direction_monitor | 4099 | U16 | 1 | |
| pid_feedback_value_monitor | 4100 | U32BE | 0.1 | |
| multi_function_input_monitor | 4102 | U16 | 1 | |
| multi_function_output_monitor | 4103 | U16 | 1 | |
| output_frequency_monitor_after_conversion | 4104 | U32BE | 0.01 | |
| real_frequency_monitor | 4106 | U32BE | 0.01 | Hz |
| torque_reference_monitor | 4108 | U16 | 1 | % |
| torque_bias_monitor | 4109 | U16 | 1 | % |
| output_torque_monitor | 4111 | U16 | 1 | % |
| output_voltage_monitor | 4112 | U16 | 0.1 | V |
| input_power_monitor | 4113 | U16 | 0.1 | kW |
| integrated_power_monitor | 4114 | U32BE | 1 | |
| total_run_time_monitor | 4116 | U32BE | 1 | h |
| total_power_on_time_monitor | 4118 | U32BE | 1 | h |
| fin_temperature_monitor | 4120 | U16 | 0.1 | °C |
| life_assessment_monitor | 4124 | U16 | 1 | |
| dc_voltage_monitor | 4133 | U16 | 0.1 | V |
| regenerative_braking_load_rate_monitor | 4134 | U16 | 0.1 | % |
| electronic_thermal_load_rate_monitor | 4135 | U16 | 0.1 | % |
| terminals | RS+/RS- on the control circuit terminal block |
| termination | Built-in terminating resistor: 120 Ω, enabled via slide switch |
| connector | Control circuit terminal block |
| shield/ground | Use a shielded cable and connect it to the terminal SC. |
| max registers/read | 16 |
| response timeout | 0 ms |
| inter-frame delay | 0 ms |
| broadcast | supported |
| protocol notes | Simultaneous broadcast to up to five groups is supported by setting the slave address to 0. |
| FC 43 device ID | not supported |
| power | Single-phase 200 to 240 VAC, 3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC |
| environment | Operating ambient temperature: -10 to 50°C, Operating ambient humidity: 20% to 90% (with no condensation), Location: At a maximum altitude of 1,000 m, indoors (without corrosive gases or dust) |
| certifications | CE, UKCA, UL, CA, KC, RCM |
| doc revision | I666-E1-03 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.