Omron MX2 (Type V2) inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
output_frequency_setting0U32BE0.01
inverter_status_a2U161
inverter_status_b3U161
inverter_status_c4U161
pid_feedback5U160.01
output_frequency_monitor4096U32BE0.01Hz
output_current_monitor4098U160.01A
run_direction_monitor4099U161
pid_feedback_value_monitor4100U32BE0.1
multi_function_input_monitor4102U161
multi_function_output_monitor4103U161
output_frequency_monitor_after_conversion4104U32BE0.01
real_frequency_monitor4106U32BE0.01Hz
torque_reference_monitor4108U161%
torque_bias_monitor4109U161%
output_torque_monitor4111U161%
output_voltage_monitor4112U160.1V
input_power_monitor4113U160.1kW
integrated_power_monitor4114U32BE1
total_run_time_monitor4116U32BE1h
total_power_on_time_monitor4118U32BE1h
fin_temperature_monitor4120U160.1°C
life_assessment_monitor4124U161
dc_voltage_monitor4133U160.1V
regenerative_braking_load_rate_monitor4134U160.1%
electronic_thermal_load_rate_monitor4135U160.1%

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 01,03,05,06,08,15,16,23; Silent Interval 0 to 1,000 ms selectable via parameter C078.

bench facts as documented (unverified)
terminalsRS+/RS- on the control circuit terminal block
terminationBuilt-in terminating resistor: 120 Ω, enabled via slide switch
connectorControl circuit terminal block
shield/groundUse a shielded cable and connect it to the terminal SC.
max registers/read16
response timeout0 ms
inter-frame delay0 ms
broadcastsupported
protocol notesSimultaneous broadcast to up to five groups is supported by setting the slave address to 0.
FC 43 device IDnot supported
powerSingle-phase 200 to 240 VAC, 3-phase 200 to 240 VAC, 3-phase 380 to 480 VAC
environmentOperating ambient temperature: -10 to 50°C, Operating ambient humidity: 20% to 90% (with no condensation), Location: At a maximum altitude of 1,000 m, indoors (without corrosive gases or dust)
certificationsCE, UKCA, UL, CA, KC, RCM
doc revisionI666-E1-03

generated by gemini:gemini-3.5-flash · harvested from https://files.omron.eu/downloads/latest/manual/en/i666_mx2-ev2_users_manual_en.pdf?v=2 (Omron); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.