Onicon FT-3000 flow meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
full_scale_flow_rate0F32BE1display unit
flow_rate_percent_full_scale2F32BE1%
flow_rate4F32BE1display unit
flow_velocity6F32BE1ft/s or m/s
t_plus_total_forward_flow_totalizer8U32BE1display unit
t_plus_overflow_decimal_point10U161
p_plus_partial_forward_flow_totalizer11U32BE1display unit
p_plus_overflow_decimal_point13U161
t_minus_total_reverse_flow_totalizer14U32BE1display unit
t_minus_overflow_decimal_point16U161
p_minus_partial_reverse_flow_totalizer17U32BE1display unit
p_minus_overflow_decimal_point19U161
process_flags20U161
samples_for_average_flow21U161samples
equivalent_resistance_e1_common22U161
equivalent_resistance_e2_common23U161
voltage_e1_common24I161mV
voltage_e2_common25I161mV
voltage_recharging_terminals26U161mV
residual_battery_capacity27U161%
cpu_temperature28I161F or C
board_temperature_t129I161F or C
board_temperature_t230I161F or C
sensor_coil_temperature31I161F or C
latest_sensor_test_result_code32U161
active_alarms_count33U161

link settings as documented (unverified): RTU; default 19200 8E1; unit ID 1; FC 04,05,08; Device address range is 001 - 255. Default parity is Even. Default baud rate is 19200. MODBUS Reply Delay default is 20 ms (range 0 - 99 ms). MODBUS Timeout Interval default is 2 (valid settings: 1, 2, 3, 5).

bench facts as documented (unverified)
terminals26 - Shield, 27 - RS485 Common, 28 - A - RS485 (+), 29 - B - RS485 (-)
A/B polarityRS485 network cable connections are polarity sensitive (+ to + and - to -)
terminationField settable 120Ω resistor via switches 1 and 2
shield/groundShield wires must not be connected to the FT-3000 Series. Shield drain wire should be left unterminated at the end of the cable and connected to earth only at the network master controller.
wiring notesTransceiver is 3-wire, half-duplex, 1/8 unit load. Max of 32 devices per segment.
broadcastnot supported
protocol notesMODBUS Reply Delay is configurable from 0 to 99 ms.
doc revisionDOC-0001665 Rev.F

generated by gemini:gemini-3.5-flash · harvested from https://www.onicon.com/wp-content/uploads/ft-3000-series-modbus-supplement-doc-0001665.pdf (Onicon); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.