Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| full_scale_flow_rate | 0 | F32BE | 1 | display unit |
| flow_rate_percent_full_scale | 2 | F32BE | 1 | % |
| flow_rate | 4 | F32BE | 1 | display unit |
| flow_velocity | 6 | F32BE | 1 | ft/s or m/s |
| t_plus_total_forward_flow_totalizer | 8 | U32BE | 1 | display unit |
| t_plus_overflow_decimal_point | 10 | U16 | 1 | |
| p_plus_partial_forward_flow_totalizer | 11 | U32BE | 1 | display unit |
| p_plus_overflow_decimal_point | 13 | U16 | 1 | |
| t_minus_total_reverse_flow_totalizer | 14 | U32BE | 1 | display unit |
| t_minus_overflow_decimal_point | 16 | U16 | 1 | |
| p_minus_partial_reverse_flow_totalizer | 17 | U32BE | 1 | display unit |
| p_minus_overflow_decimal_point | 19 | U16 | 1 | |
| process_flags | 20 | U16 | 1 | |
| samples_for_average_flow | 21 | U16 | 1 | samples |
| equivalent_resistance_e1_common | 22 | U16 | 1 | kΩ |
| equivalent_resistance_e2_common | 23 | U16 | 1 | kΩ |
| voltage_e1_common | 24 | I16 | 1 | mV |
| voltage_e2_common | 25 | I16 | 1 | mV |
| voltage_recharging_terminals | 26 | U16 | 1 | mV |
| residual_battery_capacity | 27 | U16 | 1 | % |
| cpu_temperature | 28 | I16 | 1 | F or C |
| board_temperature_t1 | 29 | I16 | 1 | F or C |
| board_temperature_t2 | 30 | I16 | 1 | F or C |
| sensor_coil_temperature | 31 | I16 | 1 | F or C |
| latest_sensor_test_result_code | 32 | U16 | 1 | |
| active_alarms_count | 33 | U16 | 1 |
| terminals | 26 - Shield, 27 - RS485 Common, 28 - A - RS485 (+), 29 - B - RS485 (-) |
| A/B polarity | RS485 network cable connections are polarity sensitive (+ to + and - to -) |
| termination | Field settable 120Ω resistor via switches 1 and 2 |
| shield/ground | Shield wires must not be connected to the FT-3000 Series. Shield drain wire should be left unterminated at the end of the cable and connected to earth only at the network master controller. |
| wiring notes | Transceiver is 3-wire, half-duplex, 1/8 unit load. Max of 32 devices per segment. |
| broadcast | not supported |
| protocol notes | MODBUS Reply Delay is configurable from 0 to 99 ms. |
| doc revision | DOC-0001665 Rev.F |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.