Parker AC10 inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
output_frequency4096U160.01Hz
output_voltage4097U161V
output_current4098U160.01A
bus_voltage4100U161V
output_torque_percent4102U160.1%
radiator_temperature4103U161°C
pid_given_value4104U160.1
pid_feedback_value4105U160.1
integer_power_value4106U161kW
di_terminal_status4107U161
terminal_output_status4108U161
ai1_value4109U161
ai2_value4110U161
ao1_percent4117U160.01%
current_speed4119U161rpm
accurate_power_value4120U160.1kW

link settings as documented (unverified): RTU/ASCII; default 9600 8N1; unit ID 1; FC 03,06; RS485 Half-duplex communication mode. Daisy chain structure is adopted by 485 Bus-line.

⚠ FAILURE OR IMPROPER SELECTION OR IMPROPER USE OF THE PRODUCTS DESCRIBED HEREIN OR RELATED ITEMS CAN CAUSE DEATH, PERSONAL INJURY AND PROPERTY DAMAGE. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsA+ and B-
A/B polarityA+ positive polarity of differential signal, B- negative polarity of differential signal
terminationTerminal resistance of 120 Ohm will be adopted for terminal of RS485 network
connectorControl terminals
shield/groundNo direct grounding shall be allowed for any point of RS485 network. All the equipment in the network shall be well grounded via their own grounding terminal.
max registers/read9
broadcastsupported
protocol notesAllows to read six function codes and write only one function code.
firmware register0x0105
powerInput terminals of three-phase 400V AC voltage (R/L1 and S/L2 terminals for single-phase)
doc revisionHA502320U001 Issue 1

generated by gemini:gemini-3.5-flash · harvested from https://drives-online.com/pdf/parker/HA502320U001.pdf (Parker); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.