Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| input_relative_value | 0 | U32BE | 1 | |
| maximum_value | 2 | U32BE | 1 | |
| minimum_value | 4 | U32BE | 1 | |
| total_value | 6 | U32BE | 1 | |
| setpoint_1_value | 8 | U32BE | 1 | |
| setpoint_2_value | 10 | U32BE | 1 | |
| setpoint_3_value | 12 | U32BE | 1 | |
| setpoint_4_value | 14 | U32BE | 1 | |
| setpoint_1_band_dev_value | 16 | U32BE | 1 | |
| setpoint_2_band_dev_value | 18 | U32BE | 1 | |
| setpoint_3_band_dev_value | 20 | U32BE | 1 | |
| setpoint_4_band_dev_value | 22 | U32BE | 1 | |
| setpoint_output_register | 24 | U16 | 1 | |
| manual_mode_register | 25 | U16 | 1 | |
| reset_output_register | 26 | U16 | 1 | |
| analog_output_register | 27 | U16 | 1 | |
| input_absolute_value | 28 | U32BE | 1 | |
| input_offset_value | 30 | U32BE | 1 |
| max registers/read | 32 |
| protocol notes | Maximum 32 register writes and 32 register reads. |
| model register | 41001 |
| firmware register | 41001 |
| identification notes | Slave ID register 41001-41010 contains model 'RLC-PAX2A' and version number. |
| doc revision | 4/15/13 LP0931A |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.