verified connector library

Regin Corrigo/Exigo heating controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
outdoor_temp1I160.1°C
heating_primary_supply_temp358I160.1°C
heating_primary_return_temp359I160.1°C
cooling_primary_supply_temp360I160.1°C
cooling_primary_return_temp361I160.1°C
supply_temp_hs12I160.1°C
outdoor_compensated_setpoint_supply_temp_hs13I160.1°C
room_temp_hs14I160.1°C
setpoint_room_temp_hs117I160.1°C
return_temp_hs15I160.1°C
control_signal_hs1_cv153I160.1V
controller_output_hs1160I160.1%
supply_temp_hs26I160.1°C
outdoor_compensated_setpoint_supply_temp_hs27I160.1°C
room_temp_hs28I160.1°C
return_temp_hs29I160.1°C
control_signal_hs2_cv154I160.1
controller_output_hs2161I160.1
supply_temp_hs310I160.1°C
outdoor_compensated_setpoint_supply_temp_hs311I160.1°C
room_temp_hs312I160.1°C
return_temp_hs313I160.1°C
control_signal_hs3_cv155I160.1
controller_output_hs3162I160.1
supply_temp_hwc114I160.1°C
setpoint_supply_hwc152I160.1
control_signal_hw1_cv156I160.1
controller_output_hw1163I160.1
supply_temp_hwc215I160.1°C
setpoint_supply_hwc253I160.1
control_signal_hwc2_cv157I160.1
controller_output_hwc2164I160.1
supply_temp_hp116I160.1°C
return_temp_hp117I160.1°C
boiler_temp18I160.1
boiler_return_temp356I160.1
boiler_supply_temp394I160.1
difference_pressure19I160.1
wind_speed20I160.1
energy_consumption_mwh65I160.1
water_consumption_m366I160.1
power_usage_instant27I160.1
cold_water_1_consumption_m367I160.1
cold_water_1_flow30I160.1
cold_water_2_consumption_m368I160.1
cold_water_2_flow36I160.1
electric_consumption_mwh69I160.1
leakage_power42I160.1

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 01,02,03,04,05,06,15,16; Corrigo/Exigo uses the same port for communication via Modbus and via EXOline. The input port will automatically adapt itself after approx. 1 second and remain in EXO-mode until no communication has taken place for 10 seconds, after which it will revert to Modbus mode.

bench facts as documented (unverified)
wiring notesFor Modbus, the bottom layer can be RS485, RS422 or RS232.
max registers/read47
inter-frame delay16 ms
protocol notesThe Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two messages. When communicating with more than one controller on the same RS485 line, the master must wait for a minimum of 14 character times (16 ms at 9600 bps) between the answer and the first question for the next controller. The controller is limited to 10 fast communications every 30 seconds; other communications will have a delayed answer time of approximately 1 second.
doc revisionRevision 14, January 2015
firmware applicabilityFrom version 3.4
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [9600], default 9600, default unit ID 1, framing RTU, parity N, stop bits 1 — confirmed by Regin Corrigo heating and Exigo manual (Revision 14, January 2015)
  • confirmed: EXOline auto-adapt port behavior (adapts after ~1s, remains in EXO-mode until 10s inactivity, then reverts to Modbus) — confirmed by Regin Corrigo heating and Exigo manual and SAUTER flexotron800 V2 Heating manual
  • confirmed: Inter-frame delay and multi-controller RS485 line timing (3.5 character times / 4 ms at 9600 bps between messages, 14 character times / 16 ms at 9600 bps between answer and next question) — confirmed by Regin Corrigo heating and Exigo manual
  • confirmed: Communication limits (limited to 10 fast communications every 30 seconds, others delayed by ~1 second) — confirmed by Regin Corrigo heating and Exigo manual
  • confirmed: Maximum read registers limit of 47 — confirmed by Regin Corrigo heating and Exigo manual
  • confirmed: outdoor_temp @ 1 (Input Register, type 4) — confirmed by Regin Corrigo heating and Exigo manual
  • confirmed: supply_temp_hs1 @ 2 (Input Register, type 4) — confirmed by Regin Corrigo heating and Exigo manual
  • confirmed: outdoor_compensated_setpoint_supply_temp_hs1 @ 3 (Input Register, type 4) — confirmed by Regin Corrigo heating and Exigo manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.