Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| outdoor_temp | 1 | I16 | 0.1 | °C |
| heating_primary_supply_temp | 358 | I16 | 0.1 | °C |
| heating_primary_return_temp | 359 | I16 | 0.1 | °C |
| cooling_primary_supply_temp | 360 | I16 | 0.1 | °C |
| cooling_primary_return_temp | 361 | I16 | 0.1 | °C |
| supply_temp_hs1 | 2 | I16 | 0.1 | °C |
| outdoor_compensated_setpoint_supply_temp_hs1 | 3 | I16 | 0.1 | °C |
| room_temp_hs1 | 4 | I16 | 0.1 | °C |
| setpoint_room_temp_hs1 | 17 | I16 | 0.1 | °C |
| return_temp_hs1 | 5 | I16 | 0.1 | °C |
| control_signal_hs1_cv | 153 | I16 | 0.1 | V |
| controller_output_hs1 | 160 | I16 | 0.1 | % |
| supply_temp_hs2 | 6 | I16 | 0.1 | °C |
| outdoor_compensated_setpoint_supply_temp_hs2 | 7 | I16 | 0.1 | °C |
| room_temp_hs2 | 8 | I16 | 0.1 | °C |
| return_temp_hs2 | 9 | I16 | 0.1 | °C |
| control_signal_hs2_cv | 154 | I16 | 0.1 | |
| controller_output_hs2 | 161 | I16 | 0.1 | |
| supply_temp_hs3 | 10 | I16 | 0.1 | °C |
| outdoor_compensated_setpoint_supply_temp_hs3 | 11 | I16 | 0.1 | °C |
| room_temp_hs3 | 12 | I16 | 0.1 | °C |
| return_temp_hs3 | 13 | I16 | 0.1 | °C |
| control_signal_hs3_cv | 155 | I16 | 0.1 | |
| controller_output_hs3 | 162 | I16 | 0.1 | |
| supply_temp_hwc1 | 14 | I16 | 0.1 | °C |
| setpoint_supply_hwc1 | 52 | I16 | 0.1 | |
| control_signal_hw1_cv | 156 | I16 | 0.1 | |
| controller_output_hw1 | 163 | I16 | 0.1 | |
| supply_temp_hwc2 | 15 | I16 | 0.1 | °C |
| setpoint_supply_hwc2 | 53 | I16 | 0.1 | |
| control_signal_hwc2_cv | 157 | I16 | 0.1 | |
| controller_output_hwc2 | 164 | I16 | 0.1 | |
| supply_temp_hp1 | 16 | I16 | 0.1 | °C |
| return_temp_hp1 | 17 | I16 | 0.1 | °C |
| boiler_temp | 18 | I16 | 0.1 | |
| boiler_return_temp | 356 | I16 | 0.1 | |
| boiler_supply_temp | 394 | I16 | 0.1 | |
| difference_pressure | 19 | I16 | 0.1 | |
| wind_speed | 20 | I16 | 0.1 | |
| energy_consumption_mwh | 65 | I16 | 0.1 | |
| water_consumption_m3 | 66 | I16 | 0.1 | |
| power_usage_instant | 27 | I16 | 0.1 | |
| cold_water_1_consumption_m3 | 67 | I16 | 0.1 | |
| cold_water_1_flow | 30 | I16 | 0.1 | |
| cold_water_2_consumption_m3 | 68 | I16 | 0.1 | |
| cold_water_2_flow | 36 | I16 | 0.1 | |
| electric_consumption_mwh | 69 | I16 | 0.1 | |
| leakage_power | 42 | I16 | 0.1 |
| wiring notes | For Modbus, the bottom layer can be RS485, RS422 or RS232. |
| max registers/read | 47 |
| inter-frame delay | 16 ms |
| protocol notes | The Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two messages. When communicating with more than one controller on the same RS485 line, the master must wait for a minimum of 14 character times (16 ms at 9600 bps) between the answer and the first question for the next controller. The controller is limited to 10 fast communications every 30 seconds; other communications will have a delayed answer time of approximately 1 second. |
| doc revision | Revision 14, January 2015 |
| firmware applicability | From version 3.4 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.