verified connector library

Regin Corrigo/Exigo heating controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
outdoor_temp1I160.1°C
heating_primary_supply_temp358I160.1°C
heating_primary_return_temp359I160.1°C
cooling_primary_supply_temp360I160.1°C
cooling_primary_return_temp361I160.1°C
supply_temp_hs12I160.1°C
outdoor_compensated_setpoint_supply_temp_hs13I160.1°C
room_temp_hs14I160.1°C
setpoint_room_temp_hs117I160.1°C
return_temp_hs15I160.1°C
control_signal_hs1_cv153I160.1V
controller_output_hs1160I160.1%
supply_temp_hs26I160.1°C
outdoor_compensated_setpoint_supply_temp_hs27I160.1°C
room_temp_hs28I160.1°C
return_temp_hs29I160.1°C
control_signal_hs2_cv154I160.1
controller_output_hs2161I160.1
supply_temp_hs310I160.1°C
outdoor_compensated_setpoint_supply_temp_hs311I160.1°C
room_temp_hs312I160.1°C
return_temp_hs313I160.1°C
control_signal_hs3_cv155I160.1
controller_output_hs3162I160.1
supply_temp_hwc114I160.1°C
setpoint_supply_hwc152I160.1
control_signal_hw1_cv156I160.1
controller_output_hw1163I160.1
supply_temp_hwc215I160.1°C
setpoint_supply_hwc253I160.1
control_signal_hwc2_cv157I160.1
controller_output_hwc2164I160.1
supply_temp_hp116I160.1°C
return_temp_hp117I160.1°C
boiler_temp18I160.1
boiler_return_temp356I160.1
boiler_supply_temp394I160.1
difference_pressure19I160.1
wind_speed20I160.1
energy_consumption_mwh65I160.1
water_consumption_m366I160.1
power_usage_instant27I160.1
cold_water_1_consumption_m367I160.1
cold_water_1_flow30I160.1
cold_water_2_consumption_m368I160.1
cold_water_2_flow36I160.1
electric_consumption_mwh69I160.1
leakage_power42I160.1

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 01,02,03,04,05,06,15,16; Corrigo/Exigo uses the same port for communication via Modbus and via EXOline. The input port will automatically adapt itself after approx. 1 second and remain in EXO-mode until no communication has taken place for 10 seconds, after which it will revert to Modbus mode.

bench facts as documented (unverified)
wiring notesFor Modbus, the bottom layer can be RS485, RS422 or RS232.
max registers/read47
inter-frame delay16 ms
protocol notesThe Modbus master must wait for a minimum of 3.5 character times (4 ms at 9600 bps) between two messages. When communicating with more than one controller on the same RS485 line, the master must wait for a minimum of 14 character times (16 ms at 9600 bps) between the answer and the first question for the next controller. The controller is limited to 10 fast communications every 30 seconds; other communications will have a delayed answer time of approximately 1 second.
doc revisionRevision 14, January 2015
firmware applicabilityFrom version 3.4

generated by gemini:gemini-3.5-flash · harvested from https://www.regincontrols.com/globalassets/pimmediafiles/documents/corrigo_exigo_heating_variables_for_exoline_modbus_and_bacnet_3.4_manu_en.pdf (Regin); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.