Reznor CLIMANAGER packaged AC controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
air_quality_voc_sensor0I161
auto_mode_set_point1I161
confort_heating_set_point2I160.1
eco_heating_set_point3I160.1
confort_cooling_set_point4I160.1
eco_cooling_set_point5I160.1
humidity_set_point6I160.1
outdoor_humidity7I160.1
supply_humidity8I160.1
return_humidity9I160.1
high_pressure_circuit_111I160.1
high_pressure_circuit_212I160.1
high_pressure_circuit_313I160.1
high_pressure_heat_recovery_circuit14I160.1
outdoor_temperature15I160.1
supply_temperature16I160.1
return_ambient_temperature18I160.1
exhaust_fresh_air_damper21I161
air_quality_co2_sensor208U161
number_of_compressors_working209U161
horas_compresor_1_c1210U161
horas_compresor_1_c2211U161
horas_compresor_1_c3212U161
horas_compresor_2_c1213U161
horas_compresor_2_c2214U161
horas_compresor_2_c3215U161
horas_compresor_cr216U161
arranques_compresor_1_c1217U161
arranques_compresor_1_c2218U161
arranques_compresor_1_c3219U161
arranques_compresor_2_c1220U161
arranques_compresor_2_c2221U161
arranques_compresor_2_c3222U161
arranques_compresor_cr223U161
actual_supply_fan_flow_l228U161
actual_supply_fan_flow_h229U161
actual_return_fan_flow_l230U161
actual_return_fan_flow_h231U161

link settings as documented (unverified): RTU/TCP; default 9600 8N1

bench facts as documented (unverified)
power230 Vac
environment-10ºC/+60°C
doc revisionMR_KCR_1602A_EN_EU
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms defaults (baud rate 9600, parity None, stop bits 1) — confirmed by Gfc23 parameter settings in the MR_KCR_1602A_EN_EU manual [21.4.1]
  • confirmed: framing (RTU and TCP) — confirmed by Section 10/11 of the MR_KCR_1602A_EN_EU manual stating support for RS485 (RTU) and Ethernet (TCP/IP) platforms
  • confirmed: facts (doc_revision MR_KCR_1602A_EN_EU, environment -10ºC/+60°C, power 230 Vac) — confirmed by the main specifications of the electronic board on Page 4 of the manual
  • confirmed: register map summary (0-based addresses) — confirmed by the BMS variables tables in Section 9 of the manual, where analog variables start at BMS address 1 (0-based address 0) and integer variables have a +208 offset (e.g., air_quality_co2_sensor at BMS address 1 + 208 = 209, which is 0-based address 208)

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.