Rosemount 5900C radar level gauge

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
device_status_10001000U32BE1
device_error1002U32BE1
device_warning1004U32BE1
device_status_40004000U32BE1
measurement_status4002U32BE1
ullage4008F32BE1
signal_strength4012F32BE1
lpg_corr_error4702U32BE1
gain5112F32BE1
ram_error6000U32BE1
fprom_error6002U32BE1
database_hreg_error6004U32BE1
other_memory_error6006U32BE1
microwave_module_error6008U32BE1
rm_error6010U32BE1
other_hardware_error6022U32BE1
configuration_error6028U32BE1
software_error6030U32BE1
ram_warning6100U32BE1
fprom_warning6102U32BE1
hreg_warning6104U32BE1
other_memory_warning6106U32BE1
mwm_warning6108U32BE1
rm_warning6110U32BE1
other_hardware_warning6122U32BE1
configuration_warning6128U32BE1
sw_warning6130U32BE1

⚠ WARNING - Substitution of components may impair Intrinsic Safety. WARNING - To prevent ignition of flammable or combustible atmospheres, disconnect power before servicing. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsX1: Tankbus in, X2: Terminate on, X3: Shield loop through, X4: Tankbus out, Test terminals
A/B polarityPolarity insensitive
terminationBuilt-in Tankbus terminator, enabled by inserting a jumper in the terminal block (X2)
connectorTwo 1/2 - 14 NPT entries; optional M20x1.5, minifast, or eurofast adapters
isolationCable shield inside the terminal compartment must be isolated; X3 connector is separated from chassis ground
shield/groundSingle grounding point for shield wire located at the power supply
powerFISCO: 9.0 - 17.5 VDC, Entity: 9.0 - 30.0 VDC. Polarity insensitive. Quiescent current draw: 51 mA (50 mA bus current draw). Lift-off minimum voltage: 9.0 VDC
environmentUse wire rated at least 5 °C above maximum ambient temperature
certificationsFISCO/Entity compliant, FM USA/Canada AIS Class I Div 1, ATEX/IECEx Ex [ia] or Ex [ib] (FISCO) / Ex [ia] (Entity), CE, FCC, IC
doc revision00809-0100-5901, Rev DD, September 2024

generated by gemini:gemini-3.5-flash · harvested from https://www.emerson.com/documents/automation/manual-rosemount-5900c-radar-level-gauge-en-81472.pdf (Emerson); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.