Schneider Altistart 48 (ATS48) soft starter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
drivecom_control_register400U161
extended_control_register402U161
drivecom_status_register458U161
extended_status_register459U161
extended_status_register_2460U161
nominal_motor_current4026U160.1
limiting_current4039U161
acceleration_ramp_time4043U161
deceleration_ramp_time4044U161
line_voltage4055U161V
motor_current4062U160.1
motor_torque4063U161
motor_thermal_state4064U161
phase_rotation_direction4065U161
state_of_logic_io4066U161
cos_phi4067U160.01
operating_time_since_last_reset4068U161
image_of_analog_output_ao4070U160.002
active_power_percent4072U161
active_power_kw4073U161
power_consumption4074U161
product_operating_time4075U161
last_fault_detected4200U161

link settings as documented (unverified): RTU; default 19200 8N1; unit ID 0; FC 03,04,06,16,65; Address 0 is used for broadcast or behaves as if configured on all addresses 1 to 31 if configured as 0. Addresses 126 and 127 are privileged.

⚠ This type of use invalidates the starter warranty (referring to LII: All protection disabled on LI3). — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRJ45 connector
termination120 Ohm + 1 nF recommended at both ends
connectorRJ45
shield/groundconnect the cable shielding to the ground of each device
wiring notesEach ATS48 integrates two 4.7 kohm pulldown resistors. Up to 27 starters can be connected if master has 4.7 kohm pulldown resistors, up to 18 if master has 470 ohm.
max registers/read30
broadcastsupported
protocol notesThe end of the frame is detected if silent for >= 3 characters.
firmware registerW4501
identification notesIdentification service (code 65) can be used to obtain manufacturer name, product name, product reference, software version, and software upgrade index.
FC 43 device IDnot supported
doc revision04/2013

generated by gemini:gemini-3.5-flash · harvested from https://download.schneider-electric.com/files?p_Doc_Ref=1623736 (Schneider Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.