Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| drivecom_control_register | 400 | U16 | 1 | |
| extended_control_register | 402 | U16 | 1 | |
| drivecom_status_register | 458 | U16 | 1 | |
| extended_status_register | 459 | U16 | 1 | |
| extended_status_register_2 | 460 | U16 | 1 | |
| nominal_motor_current | 4026 | U16 | 0.1 | |
| limiting_current | 4039 | U16 | 1 | |
| acceleration_ramp_time | 4043 | U16 | 1 | |
| deceleration_ramp_time | 4044 | U16 | 1 | |
| line_voltage | 4055 | U16 | 1 | V |
| motor_current | 4062 | U16 | 0.1 | |
| motor_torque | 4063 | U16 | 1 | |
| motor_thermal_state | 4064 | U16 | 1 | |
| phase_rotation_direction | 4065 | U16 | 1 | |
| state_of_logic_io | 4066 | U16 | 1 | |
| cos_phi | 4067 | U16 | 0.01 | |
| operating_time_since_last_reset | 4068 | U16 | 1 | |
| image_of_analog_output_ao | 4070 | U16 | 0.002 | |
| active_power_percent | 4072 | U16 | 1 | |
| active_power_kw | 4073 | U16 | 1 | |
| power_consumption | 4074 | U16 | 1 | |
| product_operating_time | 4075 | U16 | 1 | |
| last_fault_detected | 4200 | U16 | 1 |
⚠ This type of use invalidates the starter warranty (referring to LII: All protection disabled on LI3). — Starkest reads only; we never write a control register.
| terminals | RJ45 connector |
| termination | 120 Ohm + 1 nF recommended at both ends |
| connector | RJ45 |
| shield/ground | connect the cable shielding to the ground of each device |
| wiring notes | Each ATS48 integrates two 4.7 kohm pulldown resistors. Up to 27 starters can be connected if master has 4.7 kohm pulldown resistors, up to 18 if master has 470 ohm. |
| max registers/read | 30 |
| broadcast | supported |
| protocol notes | The end of the frame is detected if silent for >= 3 characters. |
| firmware register | W4501 |
| identification notes | Identification service (code 65) can be used to obtain manufacturer name, product name, product reference, software version, and software upgrade index. |
| FC 43 device ID | not supported |
| doc revision | 04/2013 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.