verified connector library

Schneider Conext Grid-Tie inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
device_state64U161
inverter_enabled65U161
device_present66U161
active_faults_flag67U161
active_fault_count68U161
fault_bitmap_069U161
configuration_errors70U32BE1
pv_input_voltage72U32BE0.001V
pv_input_current74U32BE0.001A
pv_input_power76U32BE1W
grid_ac_voltage78U32BE0.001V
grid_ac_current80U32BE0.001A
grid_ac_frequency82U160.01Hz
inverter_status83U161
grid_ac_power84U32BE1W
ac_power_to_load86U32BE1W
ac_power_to_grid88U32BE1W
energy_from_pv_this_hour96U32BE0.001kWh
pv_input_active_this_hour98U32BE1s
energy_from_pv_today100U32BE0.001kWh
pv_input_active_today102U32BE1s
energy_from_pv_this_week104U32BE0.001kWh
pv_input_active_week106U32BE1s
energy_from_pv_this_month108U32BE0.001kWh
pv_input_active_month110U32BE1s
energy_from_pv_this_year112U32BE0.001kWh
pv_input_active_year114U32BE1s
energy_from_pv_lifetime116U32BE0.001kWh
pv_input_active_lifetime118U32BE1s
grid_output_energy_this_hour120U32BE0.001kWh
grid_output_active_this_hour122U32BE1s
grid_output_energy_today124U32BE0.001kWh
grid_output_active_today126U32BE1s
grid_output_energy_this_week128U32BE0.001kWh
grid_output_active_this_week130U32BE1s
grid_output_energy_this_month132U32BE0.001kWh
grid_output_active_this_month134U32BE1s
grid_output_energy_this_year136U32BE0.001kWh
grid_output_active_this_year138U32BE1s
grid_output_energy_lifetime140U32BE0.001kWh
grid_output_active_lifetime142U32BE1s
ac_to_load_energy_this_hour144U32BE0.001kWh
ac_to_load_active_this_hour146U32BE1s
ac_to_load_energy_today148U32BE0.001kWh
ac_to_load_active_today150U32BE1s
ac_to_load_energy_this_week152U32BE0.001kWh
ac_to_load_active_this_week154U32BE1s
ac_to_load_energy_this_month156U32BE0.001kWh
ac_to_load_active_this_month158U32BE1s
ac_to_load_energy_this_year160U32BE0.001kWh
ac_to_load_active_this_year162U32BE1s
ac_to_load_energy_lifetime164U32BE0.001kWh
ac_to_load_active_lifetime166U32BE1s
ac_to_grid_energy_this_hour168U32BE0.001kWh
ac_to_grid_active_this_hour170U32BE1s
ac_to_grid_energy_today172U32BE0.001kWh
ac_to_grid_active_today174U32BE1s
ac_to_grid_energy_this_week176U32BE0.001kWh
ac_to_grid_active_this_week178U32BE1s
ac_to_grid_energy_this_month180U32BE0.001kWh
ac_to_grid_active_this_month182U32BE1s
ac_to_grid_energy_this_year184U32BE0.001kWh
ac_to_grid_active_this_year186U32BE1s
ac_to_grid_energy_lifetime188U32BE0.001kWh
ac_to_grid_active_lifetime190U32BE1s

link settings as documented (unverified): Modbus does not provide an error response when data written to a Modbus Register is out of range or invalid. To confirm that a Modbus Register is correctly written, you should read it back and compare it with the expected value.

⚠ UNINTENDED OPERATION: The use of this product with Modbus communications requires expertise in the design, operation, and programming of the device. LOSS OF CONTROL: Do not assign the same address to two Modbus devices. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
protocol notesModbus does not provide an error response when data written to a Modbus Register is out of range or invalid.
model register0x0000
serial register0x002B
firmware register0x001E
identification notesUnique ID Number is located at register 0x0014
doc revisionRevision A.4

generated by gemini:gemini-3.5-flash · harvested from https://web.archive.org/web/20170704034313/http://solar.schneider-electric.com/wp-content/uploads/2016/08/Conext-Modbus-Maps-V4.zip (Schneider Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.