verified connector library

Schneider Conext RL string inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
energy_since_commissioning2050U32BE0.1KWhr
energy_today2052U32BE0.1KWhr
energy_today_1_day_earlier2054U32BE0.1KWhr
energy_today_2_days_earlier2056U32BE0.1KWhr
energy_today_3_days_earlier2058U32BE0.1KWhr
energy_today_4_days_earlier2060U32BE0.1KWhr
energy_today_5_days_earlier2062U32BE0.1KWhr
energy_today_6_days_earlier2064U32BE0.1KWhr
operating_hours2078U32BE1Hr
operational_mode_state5888U161
temperature_1_ntc_control_board5889I160.1C
temperature_2_boost_module_15890I160.1C
temperature_3_boost_module_25891I160.1C
temperature_4_inverter_module5892I160.1C
apparent_power6129I160.1kVA
reactive_power6132I160.1kVAr
grid_voltage6136I160.1Vrms
phase_a_current6139I160.1Arms
pv1_voltage6143I160.1V
pv1_current6144I160.1A
pv1_power6145I160.1kW
grid_frequency6146U160.1Hz
dc_voltage6157U160.1V
real_power6171I160.1kW
fault_code6184U161
pv2_voltage6185I160.1V
pv2_current6186I160.1A
pv2_power6191I160.1kW

link settings as documented (unverified): RTU; default 9600 8N1; FC 03,08,16,43; Supports only the Modbus/RTU protocol. Slave address (Inverter ID) can be configured between 1 and 254.

⚠ HAZARD OF FIRE, ARC FLASH, OR ELECTRIC SHOCK FROM MULTIPLE SOURCES — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsRJ-45
terminationDIP switch on communication interface board
connectorRJ-45
shield/groundPin 8 Modbus ground
wiring notesStandard Ethernet (straight-through) patch cable may be used. Ethernet cross-over cables must not be used.
broadcastsupported
protocol notesBroadcasts are valid only with Function 16 and are triggered by setting the slave address to zero (0).
model register0x0001
serial register0x0014
identification notesFunction code 43 (Read Device Identifier) is supported.
FC 43 device IDsupported
doc revisionRevision A

generated by gemini:gemini-3.5-flash · harvested from https://solar.se.com/us/wp-content/uploads/sites/7/2021/11/Conext-RL-Using-Modbus-Application-Note.pdf (Schneider Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.