verified connector library

Schneider Conext TL string inverter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
energy_since_commissioning2050U32BE0.1kWh
energy_today2052U32BE0.1kWh
energy_today_1_day_earlier2054U32BE0.1kWh
energy_today_2_days_earlier2056U32BE0.1kWh
energy_today_3_days_earlier2058U32BE0.1kWh
energy_today_4_days_earlier2060U32BE0.1kWh
energy_today_5_days_earlier2062U32BE0.1kWh
energy_today_6_days_earlier2064U32BE0.1kWh
operating_hours2078U32BE1h
operational_mode_state5888U161Enum
temperature_1_control_board5889I160.1°C
temperature_2_boost_module_15890I160.1°C
temperature_3_boost_module_25891I160.1°C
temperature_4_inverter_module5892I160.1°C
apparent_power6129U160.1kVA
reactive_power6132I160.1kVar
inverter_vab6136I160.1V
inverter_vbc6137I160.1V
inverter_vca6138I160.1V
phase_a_current6139I160.1A
phase_b_current6140I160.1A
phase_c_current6141I160.1A
real_power_total6142I160.1kW
pv1_voltage6143I160.1V
pv1_current6144I160.1A
pv1_power6145I160.1kW
dc_voltage6157U160.1V
phase_a_frequency6168U160.1Hz
phase_b_frequency6169U160.1Hz
phase_c_frequency6170U160.1Hz
phase_a_real_power6171I160.1kW
phase_b_real_power6172I160.1kW
phase_c_real_power6173I160.1kW
fault_code6184U161
pv2_voltage6185I160.1V
pv2_current6186I160.1A
pv2_power6191I160.1kW

link settings as documented (unverified): RTU; default 9600 8N1; FC 03,16,43; Supports only Modbus/RTU protocol. Broadcasts supported with Function 16 by setting slave address to 0.

bench facts as documented (unverified)
terminalsRJ-45 and 5-position terminal block
connectorRJ-45 and terminal block
shield/groundChassis ground on terminal block pin 3, Modbus ground on pin 4, Modbus ground on RJ-45 pin 8
wiring notesProvides an RID (Remote Inverter Disable) input and a dry contact.
broadcastsupported
protocol notesUnmapped registers generate an 'Invalid Address' exception (02). Out of range writes return ExceptionCode = 02.
model register0x0001
serial register0x0014
firmware register0x0082
identification notesFunction 43 reports Manufacturer Name, Product Identification, and Product Version Number.
FC 43 device IDsupported
doc revisionRevision A
firmware applicabilityTo access certain registers (0x182F, 0xF9FB, 0xFA19, 0xFA1B, 0xFA60 to 0xFA6E), communication software version must be higher than 1.22.

generated by gemini:gemini-3.5-flash · harvested from https://solar.se.com/us/wp-content/uploads/sites/7/2021/11/Conext-TL-Using-Modbus-Application-Note.pdf (Schneider Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.