| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| scale_factor_v_voltage | 4105 | I16 | 1 | V |
| scale_factor_i_current | 4104 | I16 | 1 | |
| scale_factor_w_power | 4106 | I16 | 1 | kW |
| scale_factor_e_energy | 4107 | I16 | 1 | kWh |
| service_frequency | 4124 | I16 | 1 | Hz |
| thermal_demand_interval | 4116 | I16 | 1 | kW |
| error_bitmap | 4111 | I16 | 1 | |
| serial_number | 7001 | U16 | 1 | |
| modbus_address | 7004 | I16 | 1 | |
| power_block_demand_interval | 4117 | I16 | 1 | kW |
| power_block_demand_number_of_subintervals | 4118 | I16 | 1 | kW |
| signed_real_energy_consumption | 999 | F32BE | 1 | kWh |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.