Schneider iEM3100/iEM3200/iEM3300 energy meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
serial_number129U32BE1
meter_operation_timer2003U32BE1s
number_of_phases2013U161
number_of_wires2014U161
power_system2015U161
i1_phase_1_current2999F32BE1A
i2_phase_2_current3001F32BE1A
i3_phase_3_current3003F32BE1A
current_avg3009F32BE1A
voltage_l1_l23019F32BE1V
voltage_l2_l33021F32BE1V
voltage_l3_l13023F32BE1V
voltage_ll_avg3025F32BE1V
voltage_l1_n3027F32BE1V
voltage_l2_n3029F32BE1V
voltage_l3_n3031F32BE1V
voltage_ln_avg3035F32BE1V
active_power_phase_13053F32BE1kW
active_power_phase_23055F32BE1kW
active_power_phase_33057F32BE1kW
total_active_power3059F32BE1kW
total_reactive_power3067F32BE1kVAR
total_apparent_power3075F32BE1kVA
total_power_factor3083F32BE1
frequency3109F32BE1Hz
total_active_energy_import45099F32BE1kWh
total_active_energy_export45101F32BE1kWh
total_reactive_energy_import45103F32BE1kVARh
total_reactive_energy_export45105F32BE1kVARh
partial_active_energy_import45107F32BE1kWh
partial_reactive_energy_import45109F32BE1kVARh
active_energy_import_phase_145111F32BE1kWh
active_energy_import_phase_245113F32BE1kWh
active_energy_import_phase_345115F32BE1kWh

link settings as documented (unverified): RTU; baud 9600/19200/38400; FC 03,16,43

⚠ Do not use this device for critical control or protection of persons, animals, property or equipment. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminals0V, D0/-, D1/+
isolation4.0 kV rms
shield/groundshield
model register49
serial register129
firmware register1636
FC 43 device IDsupported
environmentOperating temperature: -25 to 70 °C (-13 to 158 °F), Storage temperature: -40 to 85 °C (-40 to 185 °F), Relative humidity: 5% to 95% RH non-condensing, Altitude: < 3000 m
accuracyActive energy: Class 1 conforming to BS/ EN/ IEC 62053-21, Class B conforming to BS/ EN 50470-3; Reactive energy: MID compliance, Class 2 conforming to BS/ EN/ IEC 62053-23
certificationsIEC 62052-31: 2015, IEC 62052-11: 2020, IEC 62053-21: 2020, IEC 62053-22: 2020, IEC 62053-23: 2020, IEC 61557-12: 2018/ AMD1: 2021
doc revisionDOCA0005EN-15, 07/2025

generated by gemini:gemini-3.5-flash · harvested from https://www.productinfo.schneider-electric.com/iem3100_iem3200_iem3300/ (Schneider Electric); manual-faithful — the document's claims, panel risk: LOW — panel concurs, no field disagreements; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.