Schneider PowerLogic PM710/PM750 meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
real_energy_total1000F32BE1
apparent_energy_total1002F32BE1
reactive_energy_total1004F32BE1
real_power_total1006F32BE1
apparent_power_total1008F32BE1
reactive_power_total1010F32BE1
power_factor_total1012F32BE1
voltage_ll_3p_average1014F32BE1
voltage_ln_3p_average1016F32BE1
current_3p_average1018F32BE1
frequency1020F32BE1
current_a1034F32BE1
current_b1036F32BE1
current_c1038F32BE1
current_n1040F32BE1
voltage_ab1054F32BE1
voltage_bc1056F32BE1
voltage_ca1058F32BE1
voltage_an1060F32BE1
voltage_bn1062F32BE1
voltage_cn1064F32BE1
real_power_a1066F32BE1
real_power_b1068F32BE1
real_power_c1070F32BE1
apparent_power_a1072F32BE1
apparent_power_b1074F32BE1
apparent_power_c1076F32BE1
reactive_power_a1078F32BE1
reactive_power_b1080F32BE1
reactive_power_c1082F32BE1
current_a_thd1084F32BE1
current_b_thd1086F32BE1
current_c_thd1088F32BE1
voltage_an_thd1092F32BE1
voltage_bn_thd1094F32BE1
voltage_cn_thd1096F32BE1
voltage_ab_thd1098F32BE1
voltage_bc_thd1100F32BE1
voltage_ca_thd1102F32BE1
real_power_total_demand_present1022F32BE1
apparent_power_total_demand_present1024F32BE1
reactive_power_total_demand_present1026F32BE1
real_power_total_demand_peak1028F32BE1
apparent_power_total_demand_peak1030F32BE1
reactive_power_total_demand_peak1032F32BE1
current_a_demand_present1042F32BE1
current_b_demand_present1044F32BE1
current_c_demand_present1046F32BE1
current_a_demand_peak1048F32BE1
current_b_demand_peak1050F32BE1
current_c_demand_peak1052F32BE1
power_factor_total_int4009I160.0001
frequency_int4013I160.01
current_a_thd_int4045I160.1
current_b_thd_int4046I160.1
current_c_thd_int4047I160.1
power_factor_total_signed_int4048I160.0001
voltage_an_thd_int4049I160.1
voltage_bn_thd_int4050I160.1
voltage_cn_thd_int4051I160.1
voltage_ab_thd_int4052I160.1
voltage_bc_thd_int4053I160.1
voltage_ca_thd_int4054I160.1

link settings as documented (unverified): RTU; baud 2400/4800/9600/19200; FC 03,04,06,16,17,43; RS485 2-wire link

bench facts as documented (unverified)
terminalsControl power supply connector, Voltage inputs, Current inputs, RS485 port (COM1), I/O
A/B polarityProper polarity must be observed for CTs and PTs
terminationOne (1) RS485 Terminator (MCT2W) included
connectorRS485 port (COM1)
isolationDigital Output: 3.0 kV rms isolation; Status Digital Inputs: 2.5 kV rms isolation
identification notesSupports Modbus command 0x11 (Report ID) returning PM710 Power Meter, and 0x2B (Read Device Identification) returning manufacturer, model, and firmware version.
FC 43 device IDsupported
powerAC: 100 to 415 ±10% V AC, 5 VA, 50 to 60 Hz; DC: 125 to 250 ±20% V DC, 3W
environmentOperating temperature: Meter -5 °C to +60 °C, Display -10 °C to +55 °C; Storage temperature: -40 °C to +85 °C; Humidity: 5 to 95% RH at 50 °C (non-condensing); Altitude: 3000 m; Pollution degree: 2
accuracyCurrent: 0.4% (1A to 6A); Voltage: 0.3% (50V to 277V); Power Factor: 0.5% (1A to 6A); Power: 0.5%; Frequency: ±0.02% (45 to 65 Hz); Real Energy: IEC 62053-22 Class 0.5S; Reactive Energy: IEC 62053-23 Class 2
certificationsCE, as per IEC 61010-1, UL508
doc revision63230-507-201A1, 03/2007
firmware applicability3.000 and later

generated by gemini:gemini-3.5-flash · harvested from https://www.ccontrols.com/support/dp/SchneiderElectricPowerMeter750.pdf (Schneider Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.