verified connector library

Schneider PowerLogic PM800-series meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
current_phase_a11700F32LE1
current_phase_b11702F32LE1
current_phase_c11704F32LE1
current_neutral11706F32LE1
current_ground11708F32LE1
current_3_phase_average11710F32LE1
voltage_a_b11712F32LE1
voltage_b_c11714F32LE1
voltage_c_a11716F32LE1
voltage_l_l_average11718F32LE1
voltage_a_n11720F32LE1
voltage_b_n11722F32LE1
voltage_c_n11724F32LE1
voltage_n_g11726F32LE1
voltage_l_n_average11728F32LE1
real_power_phase_a11730F32LE1
real_power_phase_b11732F32LE1
real_power_phase_c11734F32LE1
real_power_total11736F32LE1
reactive_power_phase_a11738F32LE1
reactive_power_phase_b11740F32LE1
reactive_power_phase_c11742F32LE1
reactive_power_total11744F32LE1
apparent_power_phase_a11746F32LE1
apparent_power_phase_b11748F32LE1
apparent_power_phase_c11750F32LE1
apparent_power_total11752F32LE1
true_power_factor_phase_a11754F32LE1
true_power_factor_phase_b11756F32LE1
true_power_factor_phase_c11758F32LE1
true_power_factor_total11760F32LE1
frequency11762F32LE1
energy_real_in11800F32LE1
energy_reactive_in11802F32LE1
energy_real_out11804F32LE1
energy_reactive_out11806F32LE1
energy_real_total11808F32LE1
energy_reactive_total11810F32LE1
energy_apparent11812F32LE1
thd_current_phase_a11960F32LE1
thd_current_phase_b11962F32LE1
thd_current_phase_c11964F32LE1
thd_current_phase_n11966F32LE1
thd_voltage_phase_a_n11968F32LE1
thd_voltage_phase_b_n11970F32LE1
thd_voltage_phase_c_n11972F32LE1
thd_voltage_phase_a_b11974F32LE1
thd_voltage_phase_b_c11976F32LE1
thd_voltage_phase_c_a11978F32LE1

link settings as documented (unverified): RTU/ASCII; default 9600 8E?; unit ID 1; RS-485 default baud rate is 9600, Ethernet option module default baud rate is 19200. Default parity is Even.

bench facts as documented (unverified)
terminalsRS-485 2-Wire or 4-Wire
wiring notesSupports RS-485 and RS-232 (EIA port)
broadcastsupported
firmware register3014
identification notesPower Meter Nameplate at register 3002
doc revisionPublic Document Revision 001
firmware applicability11.9xx

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.