Schneider PowerLogic PM800-series meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
current_phase_a11700F32LE1
current_phase_b11702F32LE1
current_phase_c11704F32LE1
current_neutral11706F32LE1
current_ground11708F32LE1
current_3_phase_average11710F32LE1
voltage_a_b11712F32LE1
voltage_b_c11714F32LE1
voltage_c_a11716F32LE1
voltage_l_l_average11718F32LE1
voltage_a_n11720F32LE1
voltage_b_n11722F32LE1
voltage_c_n11724F32LE1
voltage_n_g11726F32LE1
voltage_l_n_average11728F32LE1
real_power_phase_a11730F32LE1
real_power_phase_b11732F32LE1
real_power_phase_c11734F32LE1
real_power_total11736F32LE1
reactive_power_phase_a11738F32LE1
reactive_power_phase_b11740F32LE1
reactive_power_phase_c11742F32LE1
reactive_power_total11744F32LE1
apparent_power_phase_a11746F32LE1
apparent_power_phase_b11748F32LE1
apparent_power_phase_c11750F32LE1
apparent_power_total11752F32LE1
true_power_factor_phase_a11754F32LE1
true_power_factor_phase_b11756F32LE1
true_power_factor_phase_c11758F32LE1
true_power_factor_total11760F32LE1
frequency11762F32LE1
energy_real_in11800F32LE1
energy_reactive_in11802F32LE1
energy_real_out11804F32LE1
energy_reactive_out11806F32LE1
energy_real_total11808F32LE1
energy_reactive_total11810F32LE1
energy_apparent11812F32LE1
thd_current_phase_a11960F32LE1
thd_current_phase_b11962F32LE1
thd_current_phase_c11964F32LE1
thd_current_phase_n11966F32LE1
thd_voltage_phase_a_n11968F32LE1
thd_voltage_phase_b_n11970F32LE1
thd_voltage_phase_c_n11972F32LE1
thd_voltage_phase_a_b11974F32LE1
thd_voltage_phase_b_c11976F32LE1
thd_voltage_phase_c_a11978F32LE1

link settings as documented (unverified): RTU/ASCII; default 9600 8E?; unit ID 1; RS-485 default baud rate is 9600, Ethernet option module default baud rate is 19200. Default parity is Even.

bench facts as documented (unverified)
terminalsRS-485 2-Wire or 4-Wire
wiring notesSupports RS-485 and RS-232 (EIA port)
broadcastsupported
firmware register3014
identification notesPower Meter Nameplate at register 3002
doc revisionPublic Document Revision 001
firmware applicability11.9xx

generated by gemini:gemini-3.5-flash · harvested from https://www.ccontrols.com/support/dp/PM800.pdf (Schneider Electric); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.