Setra Power Patrol power meter
Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based
as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
interop-verified
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
| vin1_l1_n | 104 | F32BE | 1 | V |
| vin1_l2_n | 106 | F32BE | 1 | V |
| vin1_l3_n | 108 | F32BE | 1 | V |
| vin1_l1_l2 | 110 | F32BE | 1 | V |
| vin1_l2_l3 | 112 | F32BE | 1 | V |
| vin1_l3_l1 | 114 | F32BE | 1 | V |
| vin1_freq | 128 | F32BE | 1 | hertz |
| vin2_l1_n | 152 | F32BE | 1 | V |
| vin2_l2_n | 154 | F32BE | 1 | V |
| vin2_l3_n | 156 | F32BE | 1 | V |
| vin2_l1_l2 | 158 | F32BE | 1 | V |
| vin2_l2_l3 | 160 | F32BE | 1 | V |
| vin2_l3_l1 | 162 | F32BE | 1 | V |
| vin2_freq | 176 | F32BE | 1 | hertz |
| total_kwh | 324 | F32BE | 1 | kWh |
| total_kwh_plus | 326 | F32BE | 1 | kWh |
| total_kwh_minus | 328 | F32BE | 1 | kWh |
| total_kvarh | 330 | F32BE | 1 | kvarh |
| total_amperage | 352 | F32BE | 1 | A |
| total_kw | 354 | F32BE | 1 | kW |
| total_kvar | 356 | F32BE | 1 | kvar |
| total_kva | 358 | F32BE | 1 | kVA |
| total_apf | 360 | F32BE | 1 | power-factor |
| total_dpf | 362 | F32BE | 1 | power-factor |
| phase_l1_kwh | 404 | F32BE | 1 | kWh |
| phase_l1_amps | 430 | F32BE | 1 | A |
| phase_l1_kw | 432 | F32BE | 1 | kW |
| phase_l1_kvar | 434 | F32BE | 1 | kvar |
| phase_l1_kva | 436 | F32BE | 1 | kVA |
| phase_l1_apf | 438 | F32BE | 1 | power-factor |
| phase_l2_kwh | 464 | F32BE | 1 | kWh |
| phase_l2_amps | 490 | F32BE | 1 | A |
| phase_l2_kw | 492 | F32BE | 1 | kW |
| phase_l2_kvar | 494 | F32BE | 1 | kvar |
| phase_l2_kva | 496 | F32BE | 1 | kVA |
| phase_l2_apf | 498 | F32BE | 1 | power-factor |
| phase_l3_kwh | 524 | F32BE | 1 | kWh |
| phase_l3_amps | 550 | F32BE | 1 | A |
| phase_l3_kw | 552 | F32BE | 1 | kW |
| phase_l3_kvar | 554 | F32BE | 1 | kvar |
| phase_l3_kva | 556 | F32BE | 1 | kVA |
| phase_l3_apf | 558 | F32BE | 1 | power-factor |
link settings as documented (unverified): RTU/TCP; Data Format: Big-Endian (high byte first, or most significant byte first)
bench facts as documented (unverified)
| model register | 30042 |
| serial register | 30050 |
| firmware register | 30058 |
| doc revision | SS-SPM-MODBUS_G |
field reports — community-sourced, unverified (checked 2026-06-11)
- confirmed: comms framing: RTU, TCP — confirmed by Setra Power Patrol product documentation and BACnet PICS [1.3.9]
- confirmed: Data Format: Big-Endian (high byte first, or most significant byte first) — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
- confirmed: doc_revision: SS-SPM-MODBUS_G — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
- confirmed: identification registers (firmware: 30058, model: 30042, serial: 30050) — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
- confirmed: vin1 voltage and frequency registers (vin1_l1_n @ 104, vin1_l2_n @ 106, vin1_l3_n @ 108, vin1_l1_l2 @ 110, vin1_l2_l3 @ 112, vin1_l3_l1 @ 114, vin1_freq @ 128) — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
- confirmed: vin2 voltage and frequency registers (vin2_l1_n @ 152, vin2_l2_n @ 154, vin2_l3_n @ 156, vin2_l1_l2 @ 158, vin2_l2_l3 @ 160, vin2_l3_l1 @ 162, vin2_freq @ 176) — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
- confirmed: total energy and power registers (total_kwh @ 324, total_kwh_plus @ 326, total_kwh_minus @ 328, total_kvarh @ 330, total_amperage @ 352, total_kw @ 354, total_kvar @ 356, total_kva @ 358, total_apf @ 360, total_dpf @ 362) — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
- confirmed: phase L1 registers (phase_l1_kwh @ 404, phase_l1_amps @ 430, phase_l1_kw @ 432, phase_l1_kvar @ 434, phase_l1_kva @ 436, phase_l1_apf @ 438) — confirmed by Setra Power Meter Modbus Register Master List (SS-SPM-MODBUS_G)
generated by gemini:gemini-3.5-flash · harvested from https://www.setra.com/hubfs/modbus-register-list.pdf (Setra); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10
The trust ladder
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
- generated — A prompt produced it. Unproven — anyone can regenerate this.
- structure-verified — Decode path is structurally sound (addresses, widths, finite values). Does NOT prove word order or scaling.
- interop-verified — Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
- simulator-verified — Decoded correctly against a protocol emulator seeded with known-true values — catches word-order/scaling errors vs the emulator, not the physical device.
- hardware-verified x1 — Matched a real device with operator-attested readings as ground truth — the only rung that confirms word order + scaling on the wire.