Siemens OpenAir GDB/GLB181.1E/MO VAV compact controller

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
setpoint0U160.01%
override_control1U161
actual_position2U160.01%
actual_flow_rel3U160.01%
actual_flow_abs4U161m3/h
actual_pressure5U160.1Pa
command255U161
opening_direction256U161
adaptive_mode257U161
operating_mode258U161
min_position259U160.01%
max_position260U160.01%
actuator_running_time261U161s
vnom384U161m3/h
vmin385I160.01%
vmax386U160.01%
altitude_level387U161m
unit_switch388U161
backup_mode512U161
backup_position513U160.01%
backup_timeout514U161s
modbus_address763U161
baudrate764U161
transmission_format765U161
bus_termination766U161
bus_conf_command767U161
status768U161

link settings as documented (unverified): RTU; baud 9600/19200/38400/57600/76800/115200; unit ID 255; FC 03,04,06,16; Default baud rate is Auto. Default transmission format is 1-8-E-1. Maximum of 120 registers within one message.

bench facts as documented (unverified)
terminalsTerminal strip 7-pin, grid 2.00 mm
A/B polarityBus + on grey (GY), Bus - on pink (PK), REF on violet (VT)
termination120 Ohm electronically switchable
connectorPrewired cables (power / communication)
isolationgalvanically separated
wiring notesDelivered with two prewired cables.
max registers/read120
protocol notesOverwriting the bus configuration over bus uses a timeout. If '1 = Load' is not written into Reg 768 within 30 seconds, all values are discarded.
model register1408
serial register1283
powerAC 24 V ± 20 % (SELV) or AC 24 V class 2 (US), 50/60 Hz, 1 VA / 0.5 W (holding), 3 VA / 2.5 W (rotating)
environmentClass 3K5, Indoors, 0...50 °C, 5...95 % r. F. (non condensing)
accuracyDifferential pressure sensor: Zero point ± 0.2 Pa, Amplitude ± 4.5 % of the measured value, Drift ± 0.1 Pa / Year
certificationsCE, RCM, UL, cUL
doc revisionA6V10631832_en--_d (2018-04-16)

generated by gemini:gemini-3.5-flash · harvested from https://www.2kshops.com/content/pdf-siemens/GDB181.1E-3%20GLB181.1E-3%20VAV%20compact%20controller.pdf (Siemens); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.