Siemens SIRIUS 3RW5 soft starter (needs 3RW5 Modbus module)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
phase_current_l1_rms_float2497F32BE1A
phase_current_l2_rms_float2499F32BE1A
phase_current_l3_rms_float2501F32BE1A
phase_current_avg_rms_float2503F32BE1A
active_power_float2631F32BE1W
active_energy_import_total_float2657F32BE1Wh
remaining_motor_cooling_time34819U160.1s
motor_temperature_rise34821U161
line_voltage_u_l1_l234828U160.1V
line_voltage_u_l2_l334829U160.1
line_voltage_u_l3_l134830U160.1
phase_current_l1_rms34831U32BE0.01A
phase_current_l2_rms34833U32BE0.01
phase_current_l3_rms34835U32BE0.01
active_power34841U32BE0.0001kW
device_operating_hours35843U32BE1s
motor_starts_cw35845U32BE1
motor_starts_ccw35847U32BE1
motor_overload_trips35849U161
motor_operating_hours35855U32BE1

link settings as documented (unverified): RTU/TCP; default 19200 8E1; unit ID 126; FC 01,02,03,04,05,06,15,16,23; Supports automatic setting of port configuration and baud rate.

bench facts as documented (unverified)
terminals6-pin terminal connection for Modbus RTU, RJ45 socket for Modbus TCP
A/B polarityCom (GND, SC), -/A (D0, D-, RXD/TXD-N), +/B (D1, D+, RXD/TXD-P)
terminationBuilt-in 120-Ohm terminating resistor activated via jumper between Ter and +/B
shield/groundConnect cable shield to system ground with low impedance
wiring notesLine polarization via built-in 560-Ohm resistor pair activated by jumper between PU and PD
max registers/read125
response timeout5000 ms
broadcastsupported
protocol notesAccess monitoring time factory setting is 5 seconds (configurable to 5 or 10 seconds). Up to 2000 bits can be read per telegram.
model register199
serial register209
firmware register218
identification notesI&M0 device identification registers are read-only via FC03 and FC04. FC43 is explicitly not supported.
FC 43 device IDnot supported
doc revision03/2020 A5E43676481002A/RS-AC/003

generated by gemini:gemini-3.5-flash · harvested from https://cache.industry.siemens.com/dl/files/755/109753755/att_958903/v1/manual_Modbus_communication_module_3RW5_en-US.pdf?download=true (Siemens); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.