Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| phase_current_l1_rms_float | 2497 | F32BE | 1 | A |
| phase_current_l2_rms_float | 2499 | F32BE | 1 | A |
| phase_current_l3_rms_float | 2501 | F32BE | 1 | A |
| phase_current_avg_rms_float | 2503 | F32BE | 1 | A |
| active_power_float | 2631 | F32BE | 1 | W |
| active_energy_import_total_float | 2657 | F32BE | 1 | Wh |
| remaining_motor_cooling_time | 34819 | U16 | 0.1 | s |
| motor_temperature_rise | 34821 | U16 | 1 | |
| line_voltage_u_l1_l2 | 34828 | U16 | 0.1 | V |
| line_voltage_u_l2_l3 | 34829 | U16 | 0.1 | |
| line_voltage_u_l3_l1 | 34830 | U16 | 0.1 | |
| phase_current_l1_rms | 34831 | U32BE | 0.01 | A |
| phase_current_l2_rms | 34833 | U32BE | 0.01 | |
| phase_current_l3_rms | 34835 | U32BE | 0.01 | |
| active_power | 34841 | U32BE | 0.0001 | kW |
| device_operating_hours | 35843 | U32BE | 1 | s |
| motor_starts_cw | 35845 | U32BE | 1 | |
| motor_starts_ccw | 35847 | U32BE | 1 | |
| motor_overload_trips | 35849 | U16 | 1 | |
| motor_operating_hours | 35855 | U32BE | 1 |
| terminals | 6-pin terminal connection for Modbus RTU, RJ45 socket for Modbus TCP |
| A/B polarity | Com (GND, SC), -/A (D0, D-, RXD/TXD-N), +/B (D1, D+, RXD/TXD-P) |
| termination | Built-in 120-Ohm terminating resistor activated via jumper between Ter and +/B |
| shield/ground | Connect cable shield to system ground with low impedance |
| wiring notes | Line polarization via built-in 560-Ohm resistor pair activated by jumper between PU and PD |
| max registers/read | 125 |
| response timeout | 5000 ms |
| broadcast | supported |
| protocol notes | Access monitoring time factory setting is 5 seconds (configurable to 5 or 10 seconds). Up to 2000 bits can be read per telegram. |
| model register | 199 |
| serial register | 209 |
| firmware register | 218 |
| identification notes | I&M0 device identification registers are read-only via FC03 and FC04. FC43 is explicitly not supported. |
| FC 43 device ID | not supported |
| doc revision | 03/2020 A5E43676481002A/RS-AC/003 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.