Siemens VersiCharge EV charger

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
evse_error_code1600I161
ocpp_state1601U161
pcba_temperature1602I161°C
pause_state1629U161
max_charging_current_sum1633U161A
charger_phase1642U161
charging_current_phase_l11647U161A
charging_current_phase_l21648U161A
charging_current_phase_l31649U161A
charging_current_phase_sum1650U161A
charging_voltage_phase_l1_n1651U161V
charging_voltage_phase_l2_n1652U161V
charging_voltage_phase_l3_n1653U161V
current_charging_speed_l11662U161W
current_charging_speed_l21663U161W
current_charging_speed_l31664U161W
current_charging_speed_phase_sum1665U160.1W
power_factor_phase_l11666U160.01
power_factor_phase_l21667U160.01
power_factor_phase_l31668U160.01
average_power_factor1669U160.01
apparent_power_phase_l11670U161VA
apparent_power_phase_l21671U161VA
apparent_power_phase_l31672U161VA
average_apparent_power1673U161VA
reactive_power_phase_l11674U161var
reactive_power_phase_l21675U161var
reactive_power_phase_l31676U161var
average_reactive_power1677U161var
real_energy_consumed_phase_sum1692U32BE0.1Wh

link settings as documented (unverified): RTU/TCP; default 38400 8E1; unit ID 2; FC 03,06,16; Modbus RTU default address is 2 and can be modified by writing to register 0xA000. Modbus TCP port is 502.

bench facts as documented (unverified)
response timeout2000 ms
protocol notesMinimum Pollrate is 1000 ms. Information reporting on registers with dynamic data may take several cycles to update.
model register40013
serial register40008
firmware register40032
doc revisionA5E52200882-AB, 02/2023
firmware applicabilityV2.120 or higher

generated by gemini:gemini-3.5-flash · harvested from https://cache.industry.siemens.com/dl/files/359/109814359/att_1129076/v1/109814359_versicharge_wallbox_modBus_map_en-US.pdf (Siemens); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.