Socomec DIRIS I31 meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

cross-referenced (XPF (Quantum Bit Solutions))

Imported from a third-party source and NOT verified by us — not even structure-checked. An unverified claim, shown so you can find the device; trust it no more than the source it came from.

pointaddress (0-based)typescaleunit
ph_n_voltage_v1_v18443U32BE1V
current_i1_ma18457U32BE1
total_active_power_w18475I32BE1kW
total_positive_active_energy_eap_kwh19840U32BE1kWh
frequency_mhz18441U32BE1Hz
load_status18431U161
modbus_table_version50005U161
ph_n_voltage_v2_v18445U32BE1V
ph_n_voltage_v3_v18447U32BE1V
ph_ph_voltage_u12_v18451U32BE1V
ph_ph_voltage_u23_v18453U32BE1V