Solcon RVS-DX soft starter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
control_word0U161
status_word1U161
current_percent_flc2U161
voltage3U161
power_factor4U160.01
active_power5U161
frequency6U160.1
heatsink_temperature7U161
total_energy8U161
last_start_period9U161
last_start_max_current10U161
total_run_time11U161
total_number_of_starts12U161
last_trip_cause13U161
trip_current14U161
total_number_of_trips15U161

link settings as documented (unverified): default 9600 8E?; Standard RS485, Half Duplex with MODBUS Protocol. Terminals (-) & (+) must be wired to control supply for operation in communication mode. Leave terminal NC not connected.

⚠ Do not interchange line and load connections. Operating at surrounding air temp. higher than 40°C may cause damage to the starter. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsout(-), Out(+)
shield/groundTwisted shielded pair should be used, connect shield to ground a PLC/Computer side.
wiring notesUse twisted shielded pair.
protocol notesMODBUS TIME OUT range is 0.1-60 SEC., default is OFF.
powerControl Voltage: 230VAC +10%-15% or 115VAC +10%-15%, 50/60 Hz. Mains Voltage: 230-600V or 690V (for RVS-DX 390A and up), 50/60Hz.
environmentOperating temperature range: -10°C to +40°C. Relative non-condensed humidity inside the enclosure should not exceed 95%.
certificationsUL, cUL, CE, GOST-R
doc revisionVer. 26/12/2012
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: comms: baud_rates [1200, 2400, 4800, 9600], default_baud 9600, parity E — confirmed by RVS-DX Digital Soft Starter Instruction Manual
  • confirmed: facts: doc_revision 'Ver. 26/12/2012' — confirmed by RVS-DX Instruction Manual on HOS BV
  • confirmed: environment: Operating temperature range -10°C to +40°C, relative humidity up to 95% — confirmed by RVS-DX Datasheet
  • confirmed: power: Control Voltage 115VAC or 230VAC, Mains Voltage 230-600V or 690V (for 390A and up) — confirmed by RVS-DX Instruction Manual
  • confirmed: quirks: MODBUS TIME OUT range 0.1-60 SEC, default is OFF — confirmed by RVS-DXM Instruction Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.