| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| control_word | 0 | U16 | 1 | |
| status_word | 1 | U16 | 1 | |
| current_percent_flc | 2 | U16 | 1 | |
| voltage | 3 | U16 | 1 | |
| power_factor | 4 | U16 | 0.01 | |
| active_power | 5 | U16 | 1 | |
| frequency | 6 | U16 | 0.1 | |
| heatsink_temperature | 7 | U16 | 1 | |
| total_energy | 8 | U16 | 1 | |
| last_start_period | 9 | U16 | 1 | |
| last_start_max_current | 10 | U16 | 1 | |
| total_run_time | 11 | U16 | 1 | |
| total_number_of_starts | 12 | U16 | 1 | |
| last_trip_cause | 13 | U16 | 1 | |
| trip_current | 14 | U16 | 1 | |
| total_number_of_trips | 15 | U16 | 1 |
⚠ Do not interchange line and load connections. Operating at surrounding air temp. higher than 40°C may cause damage to the starter. — Starkest reads only; we never write a control register.
| terminals | out(-), Out(+) |
| shield/ground | Twisted shielded pair should be used, connect shield to ground a PLC/Computer side. |
| wiring notes | Use twisted shielded pair. |
| protocol notes | MODBUS TIME OUT range is 0.1-60 SEC., default is OFF. |
| power | Control Voltage: 230VAC +10%-15% or 115VAC +10%-15%, 50/60 Hz. Mains Voltage: 230-600V or 690V (for RVS-DX 390A and up), 50/60Hz. |
| environment | Operating temperature range: -10°C to +40°C. Relative non-condensed humidity inside the enclosure should not exceed 95%. |
| certifications | UL, cUL, CE, GOST-R |
| doc revision | Ver. 26/12/2012 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.