Sontex Supercal 531 heat meter (needs Modbus EIA-485 module)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
energy_unit100U161
energy_totalizer_heating102F32BE1Wh|kWh|MWh|MJ|GJ|BTU
energy_totalizer_tariff_1104F32BE1Wh|kWh|MWh|MJ|GJ|BTU
energy_totalizer_tariff_2106F32BE1Wh|kWh|MWh|MJ|GJ|BTU
volume_unit300U161
volume302F32BE1m3|USGallon
volume_tariff_1304F32BE1m3|USGallon
volume_tariff_2306F32BE1m3|USGallon
power_unit700U161
power702F32BE1W|kW
flow_unit710U161
flow712F32BE1m3/h
temperature_unit720U161
high_temperature722F32BE1°C
low_temperature724F32BE1°C
delta_temperature_unit730U161
delta_temperature732F32BE1K

link settings as documented (unverified): RTU/ASCII; default 19200 8E1; unit ID 1; The device address, the serial transmission mode (RTU or ASCII) and the parity can be changed over the optical interface by the Prog531 and Prog449 configuration software or via Modbus command. If no parity is set, the number of stop bits is set to 2 automatically.

⚠ Avoid electrostatic discharges during installation or handling. Modbus devices powered from a common AC source could be damaged if a mix of half-wave and full-wave rectified devices exist. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminals2x3 screw terminals (D1/D0/Common terminals for the RS-485 connection) and +12 VDC / 0 VDC
A/B polarityD0, D1
terminationThrough DIP switch S1 (120 Ω + 1nF) or with an external resistor
connectorPlug-screw terminal
isolationMains switching power supply module Model 0531A030 is completely electrically isolated. Model 0690A013 is built with a full-wave rectifier.
shield/groundConnect the shield to earth at only one point.
wiring notesDimensions 66 x 30 mm. Mounted in one of the two module slots on the mother board of the Supercal integrator.
broadcastsupported
protocol notesAfter programming new parameters, it's obligatory to open/separate the upper part with the lower of the integrator to perform a hardware reset.
model register30001
serial register40023
firmware register30003
identification notesFabrication number MET at 30001-30002, Custom ID (OEM serial number) at 40023-40024, Firmware version at 30003.
powerInternal power supply: Mains switching power supply of 531 / 449 integrator (0531A030, 230 VAC or 0690A013, 24 VAC). External power supply: 12 VDC / 150 mA.
environmentOperating temperature: 5° to 55°C. Storage temperature: -10° to 55°C (dry environment).
accuracyHigh accuracy e.g. energy, volume, power, flow, and temperature data.
doc revision0531P217 Installation Modbus Module EN 29-08-2018
firmware applicabilitySupercal 531 / Superstatic 449 firmware release FW 3.7 or higher (FW ≥ V3.7)

generated by gemini:gemini-3.5-flash · harvested from https://sontex.ch/wp-content/uploads/2019/02/supercal531-modbus-ig-en.pdf (Sontex); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.