Swegon GOLD RX/PX/CX/SD air handling unit (Gen E/F)

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
sa_air_flow3U161
ea_air_flow5U161
sa_duct_pressure7U160.1
ea_duct_pressure9U160.1
sa_ahu_filter_pressure_level26U160.1
ea_ahu_filter_pressure_level28U160.1
sa_fan_level36U160.01
ea_fan_level37U160.01
sa_fan_speed38U161
ea_fan_speed39U161
sa_voltage40U161
ea_voltage41U161
sa_fan_current42U160.001
ea_fan_current43U160.001
sa_fan_power44U160.001
ea_fan_power45U160.001
sa_fan_kwh46U161
ea_fan_kwh47U161
sa_temperature63I160.01°C
ea_temperature65I160.01°C
outdoor_temperature72I160.01°C
heat_exchanger_regulator_level90U160.01%
reheat_regulator_level93U160.01%
cool_regulator_level100U160.01%
rhx_operation_level104U160.01%
operation_level591U161
sa_low_speed_air_flow_set_point2U161
ea_low_speed_air_flow_set_point3U161
sa_high_speed_air_flow_set_point4U161
ea_high_speed_air_flow_set_point5U161
sa_low_speed_pressure_set_point18U160.1
ea_low_speed_pressure_set_point19U160.1
sa_high_speed_pressure_set_point20U160.1
ea_high_speed_pressure_set_point21U160.1
sa_temperature_set_point131I160.01%
ea_room_temperature_set_point134I160.01mBar

link settings as documented (unverified): RTU/TCP; FC 01,02,03,04,05,06,08,15,16

bench facts as documented (unverified)
firmware applicabilityApplicable to program version 1.09 and newer versions

generated by gemini:gemini-3.5-flash · harvested from https://www.swegon.com/siteassets/_product-documents/air-handling-units/gold-version-f/communication/_en/gold_e_modbus.pdf (Swegon); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-11 · recorded 2026-06-11

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.