| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| uni_firmware | 0 | I16 | 1 | |
| uni_device_location | 1 | I16 | 1 | |
| uni_offset_temperature | 5 | I16 | 0.01 | K |
| uni_offset_relative_humidity | 6 | I16 | 0.01 | % |
| uni_relative_humidity | 585 | I16 | 0.1 | % |
| uni_temperature_c | 587 | I16 | 0.01 | °C |
| uni_temperature_f | 588 | I16 | 0.01 | °F |
| use_temperature | 0 | I16 | 0.1 | |
| use_relative_humidity | 1 | I16 | 0.1 | |
| use_offset_temperature | 100 | I16 | 0.1 | K |
| use_offset_relative_humidity | 101 | I16 | 0.1 | %rH |
| use_unit_system | 400 | I16 | 1 | |
| use_firmware_version | 503 | I16 | 1 |
⚠ The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not be used in relation with any equipment that in case of a failure may threaten, directly or indirectly, human health or life or result in danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operating equipment. — Starkest reads only; we never write a control register.
| terminals | removable plug-in terminal, max. 14AWG |
| A/B polarity | In case of reversed polarity at one field device, a supply voltage short-circuit would be caused by that device. |
| connector | removable plug-in terminal |
| wiring notes | Cable entry Flextherm M20, for wire max. Ø=0.18..0.35 in., removable |
| protocol notes | Register compatibility to USE (Valid from firmware version 1.4, Jan. 2020). Via dipswitch 2.6 it is possible to change between the previous register addressing of the UNI-Modbus board to a USE compatible register assignment. |
| firmware register | 0 (Variant 1) or 503 (Variant 2) |
| identification notes | Firmware version is available at register 0 in UNI-Modbus mode or register 503 in USE-Modbus mode. |
| power | 15..24 V = (±10%) (or 24 V ~ (±10%))* SELV, max. 0,7 W (24 V =) | 1,8 VA (24 V ~) |
| environment | Ambient condition -4..+158 °F, short term condensation. IP65 according to EN 60529 |
| accuracy | Accuracy temperature ±0,3 K (typ. at 70 °F), Accuracy humidity ±2% between 10..90% rH (typ. at 70 °F) |
| certifications | CE |
| doc revision | 05/21/2026 • A160 |
| firmware applicability | Valid from firmware version 1.4, Jan. 2020 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.
To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.
Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.