Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.
Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.
| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| alarm_status_code_0 | 7040 | U16 | 1 | |
| alarm_code_1 | 7041 | U16 | 1 | |
| current_phase_a | 7042 | U16 | 1 | A |
| current_phase_b | 7043 | U16 | 1 | A |
| current_phase_c | 7044 | U16 | 1 | A |
| current_neutral | 7045 | U16 | 1 | A |
| current_gf | 7046 | U16 | 1 | A |
| voltage_a_n | 7047 | U16 | 1 | V |
| voltage_b_n | 7048 | U16 | 1 | V |
| voltage_c_n | 7049 | U16 | 1 | V |
| voltage_a_b | 7050 | U16 | 1 | V |
| voltage_b_c | 7051 | U16 | 1 | V |
| voltage_c_a | 7052 | U16 | 1 | V |
| power_kw_phase_a | 7053 | U16 | 1 | kW |
| power_kw_phase_b | 7054 | U16 | 1 | kW |
| power_kw_phase_c | 7055 | U16 | 1 | kW |
| power_kva_phase_a | 7056 | U16 | 1 | kVA |
| power_kva_phase_b | 7057 | U16 | 1 | kVA |
| power_kva_phase_c | 7058 | U16 | 1 | kVA |
| power_kw_total | 7059 | U16 | 1 | kW |
| power_kva_total | 7060 | U16 | 1 | kVA |
| power_factor_total | 7061 | U16 | 1 | % |
| energy_kva_hrs | 7062 | U32BE | 1 | kVAh |
| energy_kw_hrs | 7064 | U32BE | 1 | kWh |
| kw_signs_lead_lag_pf | 7066 | U16 | 1 | |
| energy_kw_hrs_alt | 7067 | U32BE | 1 | kWh |
| frequency | 7069 | U16 | 1 | Hz |
| negative_sequence_overvoltage | 7070 | U16 | 1 | % |
| status | 7071 | U16 | 1 | |
| special_current_phase_a | 7072 | U16 | 1 | A |
| special_current_phase_b | 7073 | U16 | 1 | A |
| special_current_phase_c | 7074 | U16 | 1 | A |
| special_neutral_current | 7075 | U16 | 1 | A |
| special_gf_current | 7076 | U16 | 1 | A |
| breaker_cycle_count | 7090 | U16 | 1 | |
| last_kwd | 7901 | U16 | 1 | kW |
| last_kvad | 7902 | U16 | 1 | kVA |
| peak_kwd | 7903 | U16 | 1 | kW |
| peak_kvad | 7904 | U16 | 1 | kVA |
| demand_period | 7905 | U16 | 1 | s |
| terminals | +24 VDC Aux Power, Sluggish Breaker Limit Switch, GF Defeat, Programmable Relay Output, Breaker Harness (Neutral, Phase C, Phase B, Phase A Actuator) |
| termination | RS485 End of Line Termination switch (ON/OFF) |
| connector | Quick-Trip Connector, USB, RS485 |
| serial register | 7022-7026 |
| firmware register | 7027-7028 |
| power | +24 VDC |
| certifications | UL, CE |
| doc revision | 4.0 |
| firmware applicability | v4.0.65 |
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.
Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.
Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.