Veichi AC10 AC drive

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire. Word order and scaling are confirmed at the hardware-verified rung and at no rung below it.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
communication_given_frequency12288U160.01Hz
communication_command_setting12289U161
state_of_ac_drive12290U161
ac_drive_fault_code12291U161
communication_given_upper_frequency12292U160.01Hz
communication_torque_setting12293U160.1%
fwd_max_frequency_limit_in_torque_control12294U160.1%
rev_max_frequency_limit_in_torque_control12295U160.1%
communication_given_pid_setting12296U160.1%
communication_given_pid_feedback12297U160.1%
fault_and_warning_code_reading12304U161
output_terminal_state12312U161
ao_output12313U161
given_frequency8448U160.01
output_frequency8449U160.01
output_current8450U160.1
input_voltage8451U160.1
output_voltage8452U160.1
mechanical_speed8453U161
given_torque8454I160.1
output_torque8455I160.1
pid_given8456U160.1
pid_feedback8457U160.1
output_power8458U160.1
bus_voltage8459U160.1
module_temperature_18460I160.1
module_temperature_28461I160.1

link settings as documented (unverified): RTU; default 9600 8N1; unit ID 1; FC 03,06; When F11.30 selects the external keyboard, the MODBUS bus (master/slave) cannot be used.

bench facts as documented (unverified)
terminalsA+, B-
termination120Ω termination resistor selectable via switch S3
wiring notesRS485 differential communication
response timeout1000 ms
inter-frame delay0 ms
protocol notesInterval over 1.5 byte before ending clears half-baked info. Interval under 3.5 byte time is considered continuation of former frame. Writing to 0x00XX writes to RAM, writing to 0x10XX writes to EEPROM.
powerS2: Single-phase 220V, T2: Three-phase 220V, T3: Three-phase 380V
environment-10 ~ +50°C (derating above 40°C, max 60°C), 5% to 95% RH (no condensation), altitude < 1000m, vibration 5.9 m/s2 (0.6 g)
certificationsIEC61800-2
field reports — community-sourced, unverified (checked 2026-06-11)
  • confirmed: Baud rates [1200, 2400, 4800, 9600, 19200, 38400, 57600], default baud 9600, default unit ID 1, framing RTU, parity N, stop bits 1 — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: When F11.30 selects the external keyboard, the MODBUS bus (master/slave) cannot be used — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: RS485 differential communication terminals A+, B- and 120Ω termination resistor selectable via switch S3 — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: Power models S2 (Single-phase 220V), T2 (Three-phase 220V), and T3 (Three-phase 380V) — confirmed by VEICHI AC10 Series Frequency Inverter Catalog and Quick Start Guide
  • confirmed: Register addresses 12288 (0x3000) for given frequency, 12289 (0x3001) for command setting, 12290 (0x3002) for state of AC drive, and 12291 (0x3003) for fault code — confirmed by VEICHI AC10 Series Frequency Inverter Manual
  • confirmed: Register addresses 8448 (0x2100) for given frequency, 8449 (0x2101) for output frequency, 8450 (0x2102) for output current, and 8451 (0x2103) for input voltage — confirmed by VEICHI AC10 Series Frequency Inverter Manual

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.

To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.

Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.