| point | address (0-based) | type | scale | unit |
|---|---|---|---|---|
| set_frequency | 8192 | U16 | 0.01 | Hz |
| command_setting | 8193 | U16 | 1 | |
| drive_status_information | 8194 | U16 | 1 | |
| drive_fault_code | 8195 | U16 | 1 | |
| upper_frequency_limit | 8196 | U16 | 0.01 | Hz |
| torque_setting | 8197 | I16 | 0.1 | % |
| torque_control_forward_speed_limit | 8198 | I16 | 0.1 | % |
| torque_control_reverse_speed_limit | 8199 | I16 | 0.1 | % |
| pid_setting | 8200 | I16 | 0.1 | % |
| pid_feedback | 8201 | I16 | 0.1 | % |
| vf_separation_voltage_setting | 8202 | I16 | 0.1 | % |
| tension_setting | 8203 | U16 | 1 | N |
| roll_diameter_setting | 8204 | U16 | 1 | mm |
| linear_speed_setting | 8205 | U16 | 1 | m/min |
| acceleration_time_1 | 8206 | U16 | 0.01 | s |
| deceleration_time_1 | 8207 | U16 | 0.01 | s |
| fault_warning_and_warning_code | 8208 | U16 | 1 | |
| torque_current_component | 8209 | I16 | 0.1 | % |
| torque_filter_time | 8210 | U16 | 0.001 | s |
| tension_pid_feedback | 8211 | U16 | 1 | % |
| communication_set_electric_torque_limit | 8212 | U16 | 1 | % |
| communication_set_power_generation_torque_limit | 8213 | U16 | 1 | % |
| terminal_output_control | 8216 | U16 | 1 | |
| ao_output | 8217 | U16 | 0.01 | |
| expanded_ao_output | 8218 | U16 | 0.01 | |
| given_frequency | 8448 | U16 | 0.01 | |
| output_frequency | 8449 | U16 | 0.01 | |
| output_current | 8450 | U16 | 0.1 | |
| input_voltage | 8451 | U16 | 0.1 | |
| output_voltage | 8452 | U16 | 0.1 | |
| mechanical_speed | 8453 | U16 | 1 | |
| given_torque | 8454 | I16 | 0.1 | |
| output_torque | 8455 | I16 | 0.1 | |
| pid_given | 8456 | I16 | 0.1 | |
| pid_feedback_value | 8457 | I16 | 0.1 | |
| output_power | 8458 | U16 | 0.1 | |
| dc_bus_voltage | 8459 | U16 | 0.1 | |
| module_temperature_1 | 8460 | I16 | 0.1 | |
| module_temperature_2 | 8461 | I16 | 0.1 | |
| input_terminal_x_connection_status | 8462 | U16 | 1 | |
| output_terminal_y_connection_status | 8463 | U16 | 1 | |
| analog_ai1_input_value | 8464 | U16 | 0.001 | |
| analog_ai2_input_value | 8465 | U16 | 0.001 | |
| pulse_signal_pul_input_value | 8467 | U16 | 0.001 | |
| analog_output_ao | 8468 | U16 | 0.01 | |
| expanded_ao_output_monitoring | 8469 | U16 | 0.01 | |
| counter_value | 8470 | U16 | 1 | |
| running_time_after_power_on | 8471 | U16 | 0.1 | |
| cumulative_running_time | 8472 | U16 | 1 | |
| ac_drive_capacity | 8473 | U16 | 0.1 | |
| rated_voltage | 8474 | U16 | 1 | |
| rated_current | 8475 | U16 | 0.1 | |
| pg_feedback_frequency | 8477 | U16 | 0.01 | |
| pid_output_value | 8479 | I16 | 0.01 | |
| encoder_feedback_angle | 8481 | U16 | 1 | |
| fault_warning_code_monitoring | 8484 | U16 | 1 | |
| cumulative_power_consumption_low_level | 8485 | U16 | 1 | |
| cumulative_power_consumption_high_level | 8486 | U16 | 1 | |
| power_factor_angle | 8487 | I16 | 1 | |
| output_frequency_upon_fault | 8706 | U16 | 0.01 | |
| output_voltage_upon_fault | 8707 | U16 | 0.1 | |
| output_current_upon_fault | 8708 | U16 | 0.1 | |
| dc_bus_voltage_upon_fault | 8709 | U16 | 0.1 | |
| module_temperature_upon_fault | 8710 | I16 | 0.1 | |
| ac_drive_status_upon_fault | 8711 | U16 | 1 | |
| running_time_after_power_up_maintenance | 9216 | U16 | 0.1 | h |
| cumulative_running_time_maintenance | 9217 | U16 | 1 | h |
| cumulative_power_on_time_hour | 9218 | U16 | 1 | h |
| cumulative_power_on_time_minute | 9219 | U16 | 1 | min |
| cooling_fan_running_time | 9220 | U16 | 1 | h |
| cooling_fan_maintenance | 9221 | U16 | 1 | % |
| main_relay_maintenance | 9223 | U16 | 1 | % |
| final_tension_setting | 9236 | U16 | 0.1 | |
| initial_roll_diameter_value | 9237 | U16 | 1 | |
| current_value_of_linear_velocity | 9238 | U16 | 0.1 | |
| current_value_of_roll_diameter | 9239 | U16 | 1 | |
| tension_channel_torque_set_value | 9240 | I16 | 0.1 | |
| tension_pid_given | 9241 | I16 | 0.1 | |
| tension_pid_feedback_monitoring | 9242 | I16 | 0.1 | |
| tension_pid_output | 9243 | I16 | 1 | |
| static_friction_compensation_value | 9244 | I16 | 0.1 | |
| dynamic_friction_compensation_value | 9245 | I16 | 0.1 | |
| total_friction_compensation_value | 9246 | I16 | 0.1 |
| terminals | A+ and B- (Group 1), RJ45 (Group 2) |
| A/B polarity | A+ positive, B- negative |
| termination | 120 Ohm terminal resistance can be connected via DIP switch |
| connector | Screw terminals for A+/B-, RJ45 for Group 2 |
| shield/ground | Shielded twisted pair cable recommended, ground terminal PE |
| wiring notes | RS485 communication is standard. |
| max registers/read | 20 |
| response timeout | 1000 ms |
| broadcast | supported |
| protocol notes | For broadcast transmission, the slave station does not send a response message. |
| firmware register | C02.60 |
| power | S2: Single-phase 200 V-240 V 50/60 Hz; T2: Three-phase 200 V-240 V 50/60 Hz; T3: Three-phase 380 V-480 V 50/60 Hz; T6: Three-phase 660 V-690 V 50/60 Hz |
| environment | Altitude < 1000 m (derated by 1% per 100 m above 1000 m); Temperature: -10°C to +50°C (derated above 40°C, max 60°C); Humidity: 5% RH to 95% RH (no condensation); Vibration: 5.9 m/s² (0.6 G) at 9 Hz - 200 Hz; Storage temperature: -30°C to +60°C; Protection level: IP20; Pollution degree: II; Cooling method: Forced air cooling |
| accuracy | Output frequency accuracy: ±0.5% of Max Freq. |
| certifications | IEC61800-2 |
| doc revision | V1.0 (Aug.2021 / Dec.2022) |
⚠ disputed: set_frequency @ 8192 — disputed by Weintek/Tecnolog integration guides which state that frequency setting is mapped to 3000H (12288 decimal) and control command to 3001H (12289 decimal) depending on the active communication table
Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.
If your device isn't here, upload its register map. Generation is free, and the connector keeps the rung it earns under testing.
To prove a connector against your own device, order hardware verification. If it doesn't verify, you don't pay.
Platform builders can license the verified library: machine-readable maps, the firmware matrix, API access.