verified connector library

Veris E50H2/E50H5 power meter

Register map(s) for this device, each at the trust rung it earned. Addresses are 0-based as on the wire; word order and scaling are only confirmed at the hardware-verified rung.

interop-verified

Read + decoded cleanly over a real network vs an independent third-party Modbus test server (transport and framing; reads are remapped into the server's register window, so the map's own addresses are NOT exercised). Does NOT prove word order/scaling against the actual device.

pointaddress (0-based)typescaleunit
real_energy_consumption1F32BE1
total_real_power2F32BE1
total_reactive_power3F32BE1
total_apparent_power4F32BE1
total_power_factor5F32BE1
voltage_ll_average6F32BE1
voltage_ln_average7F32BE1
current_average8F32BE1
real_power_phase_a9F32BE1
real_power_phase_b10F32BE1
real_power_phase_c11F32BE1
power_factor_phase_a12F32BE1
power_factor_phase_b13F32BE1
power_factor_phase_c14F32BE1
voltage_phase_ab15F32BE1
voltage_phase_bc16F32BE1
voltage_phase_ac17F32BE1
voltage_phase_an18F32BE1
voltage_phase_bn19F32BE1
voltage_phase_cn20F32BE1
current_phase_a21F32BE1
current_phase_b22F32BE1
current_phase_c23F32BE1
frequency25F32BE1
apparent_energy_consumption26F32BE1
reactive_energy_consumption27F32BE1
apparent_power_phase_a28F32BE1
apparent_power_phase_b29F32BE1
apparent_power_phase_c30F32BE1
reactive_power_phase_a31F32BE1
reactive_power_phase_b32F32BE1
reactive_power_phase_c33F32BE1
real_power_present_demand34F32BE1
reactive_power_present_demand35F32BE1
apparent_power_present_demand36F32BE1
real_power_maximum_demand37F32BE1
reactive_power_maximum_demand38F32BE1
apparent_power_maximum_demand39F32BE1
pulse_count_140F32BE1
pulse_count_241F32BE1
real_energy_consumption_phase_a42F32BE1
real_energy_consumption_phase_b43F32BE1
real_energy_consumption_phase_c44F32BE1
theoretical_maximum_system_power45F32BE1

link settings as documented (unverified): MS/TP; default 76800 8??; unit ID 1; The device uses BACnet MS/TP protocol over RS-485.

⚠ LOSS OF CONTROL: Assure that the system will reach a safe state during and after a control path failure. Separate or redundant control paths must be provided for critical control functions. Test the effect of transmission delays or failures of communication links. — Starkest reads only; we never write a control register.

bench facts as documented (unverified)
terminalsTerminal Block Screw Torque: 0.37 to 0.44 ft-lb (0.5 to 0.6 N-m). Terminal Block Wire Size: 24 to 14 AWG (0.2 to 2.1 mm²)
A/B polarityRS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull down to Shield (RS-485 signal ground).
terminationUse 120 Ω termination resistors at each end of the bus (not included).
connector2-wire RS-485
shield/groundShield is not internally connected to Earth Ground. Connect Shield to Earth Ground somewhere on the RS-485 bus.
wiring notesRS-485 slave port allows the power meter to be connected in a daisy chain with up to 63 2-wire devices.
protocol notesWhen writing values to the Present_Value properties of Analog_Value BACnet objects, there is a delay of up to about two seconds to validate and store the new value.
identification notesIdentification is handled via BACnet Device Object properties: Object_Name, Model_Name, and Firmware_Revision.
powerAC: 5 VA max.; 90 V min. UL Maximum: 600 VL-L (347 VL-N); CE Maximum: 300 VL-N. DC: 3 W max.; UL and CE: 125 to 300VDC
environmentOperating Temperature Range: -30 to 70 °C (-22 to 158 °F); Storage Temperature Range: -40 to 85 °C (-40 to 185 °F); Humidity Range: <95% RH non-condensing; Altitude of Operation: 3000 m; Mounting Location: Not suitable for wet locations. For indoor use only.
accuracyReal Power and Energy: IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%; Reactive Power and Energy: IEC 62053-23 Class 2, 2%; Current: 0.4% (+0.015% per °C deviation from 25 °C) from 5% to 100% of range; Voltage: 0.4% (+0.015% per °C deviation from 25 °C) from 90 VL-N to 600 VacL-L
certificationsUL 508, IEC/EN 61010-1, CE, FCC part 15 Class B, EN 55011/EN 61000 Class B, EN 61000 Class A, CSA 22.2 No. 14-05
doc revisionZL0071-0F

generated by gemini:gemini-3.5-flash · harvested from https://www.veris.com/ASSETS/DOCUMENTS/ITEMS/EN/e50hx_full_i0f2.pdf (Veris Industries); manual-faithful — the document's claims, panel risk: ELEVATED — panel is not confident; proved interop-verified on 2026-06-10 · recorded 2026-06-10

The trust ladder

Each rung states what it proved and what it did not. Gray until proven; green is earned by hardware only.

Have a device that isn't here? Upload its register map — generation is free, and the connector earns its rung by being proven, not claimed.

Need it proven on your own device? Hardware verification — if it doesn't verify, you don't pay.

Building a platform? License the verified library — machine-readable maps, firmware matrix, API access.